18/114 IZM circuit-breakers, IN switch-disconnectors

IN26 switch-disconnectors

2010 CA08103002Z-EN

www.eaton.com

IN40N…40…

IN40H…40…

IN63N…40…

General

Standards

IEC/EN 60947

Ambient temperature

Storage

°C -40 - +70

-40 - +70

-40 - +70

Operation (open)

°C -25 - +70

-25 - +70

-25 - +70

Built-in position

Utility category

B

Protection type

IP20, IP54 with protective cover

Direction of incoming supply

Any

Main contacts

Rated operational current = Rated uninterrupted current

I

n

= I

u

A 4000

4000

4000

Rated uninterrupted current at 50 °C

1)

I

u

A 4000

4000

4000

Rated uninterrupted current at 60 °C

1)

I

u

A 4000

4000

4000

Rated uninterrupted current at 70 °C

1)

I

u

A 3776

3776

4000

Rated impulse withstand voltage

U

imp

V AC 12000

12000

8000

Rated operational voltage

U

e

V AC 690

690

690

Use in IT electrical power networks up to U = 440 V

I

IT

kA 48

48

Use in IT electrical power networks up to U = 690 V

I

IT

kA –

Overvoltage category/pollution degree

III/3

III/3

III/3

Rated insulation voltage

U

i

V

1000

1000

1000

Switching capacity

Rated short-circuit making capacity

Up to 440 V 50/60 Hz

I

cm

kA 187

220

187

Up to 690 V 50/60 Hz

I

cm

kA 187

220

187

Rated short-time withstand current 50/60 Hz

t = 1 s

I

cw

kA 85

100

85

t = 3 s

I

cw

kA 65

65

65

Switching times

Total opening delay

ms 30

30

40

Closing delay

ms 35

35

35

Closing delay electrical (via closing release)

ms 40

40

40

Opening delay electrical ( via shunt release /

undervoltage release)

ms 35/70

35/70

35/70

Durability

Mechanical, without maintenance

Operations

5000

5000

5000

Mechanical, with maintenance

Operations

8000

8000

8000

Electrical, without maintenance

Operations

3000

3000

3000

Electrical, with maintenance

Operations

3000

3000

3000

Maximum operating frequency

Operations/h

60

60

60

Heat dissipation at rated operational current I

n

3-phase symmetric loading

Fixed

W 560

560

380

Withdrawable

W 1100

1100

750

Weight

Fixed

3 pole

kg 83

83

108

4 pole

kg 105

105

145

Withdrawable

3 pole

kg 98

98

139

4 pole

kg 121

121

166

Empty cassette

3 pole

kg 55

55

103

4 pole

kg 64

64

103

Notes

1)

Permissible continuous current for circuit-breakers used at different temperatures within switchgear.

The expected internal temperatures can be estimated according to the applicable IEC regulations.

30˚ 30˚

30˚ 30˚

IN...