18/122 IZM circuit-breakers, IN switch-disconnectors

Minimum clearances

2010 CA08103002Z-EN

www.eaton.com

Minimumclearances

Recommended safety clearances

The following information about safety distances is intended to provide a guideline for the installation of circuit-breakers in an enclosure.

Recommended enclosure clearance and ventilation

The illustration shows a typical enclosure.

The table below lists the associated minimum distances between enclosures and ventilation openings.

This information is intended as a guideline for constructing a suitable circuit-breaker enclosure.

① Cell switch (optional)

② Locking facilities (optional)

③ Ventilation openings (do not cover!)

Enclosure clearance

To insulated surface

To grounded metal surface With cell switch or locking

facilities

mm

mm

mm

Withdrawable units a

b

0

25

0

25

0

25/75

Fixed mounted

a

b

150

30

250

70

Width

Width of cassette + 75 mm

Height

550 mm

Depth

450 mm (front control panel bay)

Ventilation

holes

160 cm

2

(800 - 3200 A)

320 cm

2

(4000 - 6300 A)

④ Top or rear vent

⑤ Rear or lower vent

100

b

b

b

a

a

a

c

e

d

d

e

c