Background Image
Table of Contents Table of Contents
Previous Page  186 / 253 Next Page
Information
Show Menu
Previous Page 186 / 253 Next Page
Page Background

14/70

Automation products

PLCs

2010

CA08103002Z-EN

www.eaton.com

Compact PLCs

CompactPLCsPLCs

Technical data

EC4P…

General

Standards

EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27

Dimensions (W x H x D)

mm 107.5 x 90 x 72 without/79 with adapter for memory card

Weight

kg

0.3

Mounting

Top-hat rail IEC/EN 60715, 35 mm or screw fixing with 3 fixing brackets

ZB4-101-GF1 (accessories)

Terminal capacity

Solid

mm

2

0.2 - 4 (

AWG 22 - 12)

Flexible with ferrule

mm

2

0.2 - 2.5 (

AWG 22 - 12)

Flat-blade screwdriver

mm 3.5 x 0.8

Max. tightening torque

Nm 0.6

Ambient climatic conditions

Operating ambient temperature

°C

-25…55,

low temperatures to IEC 60068-2-1, high temperatures to IEC 60068-2-2

Condensation

Prevent condensation by means of suitable measures

LCD display (clearly legible)

°C

0 - 55

Storage

°C

-40 - 70

Relative humidity, non-condensing (IEC/EN 60068-2-30)

%

5 - 95

Air pressure (in operation)

hPa

795 - 1080

Ambient mechanical conditions

Pollution degree

2

Degree of protection (IEC/EN 60529, EN50178, VBG 4)

IP20

Vibrations (IEC/EN 60068-2-6)

Constant amplitude 0.15 mm

Hz

10 - 57

Constant acceleration, 2 g

Hz

57 - 150

Mechanical shock resistance (IEC/EN 60068-2-27)

semi-sinusoidal 15 g/11 ms

Shocks 18

Drop to (IEC/EN 60068-2-31)

Drop

height

mm 50

Free fall, packaged (IEC/EN 60068-2-32)

m

1

Mounting position

Vertical or horizontal

Electromagnetic compatibility (EMC)

Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)

Air discharge

kV

8

Contact discharge

kV

6

Electromagnetic fields (RFI), to IEC EN 61000-4-2

V/m 10

Radio interference suppression

EN 55011 Class B, EN 55022 Class B

Burst pulses (IEC/EN 61000-4-4, Level 3)

Supply cables

kV

2

Signal cables

kV

2

Surge pulses (IEC/EN 61000-4-5, Level 2)

kV

0.5 (

supply cables, symmetrical, EASY…DC)

Line-conducted interference (IEC/EN 61000-4-6)

V

10

Insulation resistance

Clearance in air and creepage distances

EN 50178, UL 508, CSA C22.2, No. 142

Insulation resistance

EN 50178

Real-time clock accuracy/backup time

Back-up time

Backup time (hours)

Service life (years)

Accuracy of the real-time clock

s/day

Normally ± 5 (± 0.5 h ⁄ year)

Retentive memory

Write cycles of the retentive memory (minimum)

10000000 (10¹0) (

read ⁄ write cycles)

a

b

180

200

160

140

120

100

80

60

40

20

0

0

2 4

6

8

10

20

12 14

1 3

5

7

9

11 13

55

°C

25

°C

15 17 19

16 18