Background Image
Table of Contents Table of Contents
Previous Page  111 / 253 Next Page
Information
Show Menu
Previous Page 111 / 253 Next Page
Page Background

Electronic safety relays

Basic devices, contact expansion modules

2010

CA08103002Z-EN

www.eaton.com

ESR5

13/15

ESR5Basicdevices,contactexpansionmodules

Ordering

Actuating voltage Suitable for

Number of enabling

paths to IEC/EN 60204

Stop category

Signal

contacts

Part no.

Article no.

Price

See price

list

Std. pack

U

c

0

1

ESR5 electronic safety relays

Safety relays for Emergency-Stop and guard door monitoring

Single-channel

24

V DC, 24 V AC,

50/60

Hz

Cat.2according toEN954-1

PLdaccording toEN ISO13849-1

SILCL3according to IEC62061

SIL3according to IEC61508

Cat.4/PLepossibleonlywiththeaid

of faultexclusions .

4

1

ESR5-NO-41-24VAC-DC

118701

1

off

dual channel

Cat.4according toEN954-1

PLeaccording to EN ISO13849-1

SILCL3according to IEC62061

SIL3according to IEC61508

2

1

ESR5-NO-21-24VAC-DC

118700

Cat.4according toEN954-1

PLeaccording to EN ISO13849-1

SILCL3according to IEC62061

SIL3according to IEC61508

3

1

ESR5-NO-31-24VAC-DC

118702

dual-channel

24

V AC/DC, 230 V

AC/DC, 50/60 Hz

Cat.4according toEN954-1

PLeaccording to EN ISO13849-1

SILCL3according to IEC62061

SIL3according to IEC61508

3

1

ESR5-NO-31-24V-230VAC-DC

118704

1

off

230

V AC, 50/60 Hz Cat.4according toEN954-1

PLeaccording toEN ISO13849-1

SILCL3according to IEC62061

SIL3according to IEC61508

3

1

ESR5-NO-31-230VAC

119380

Safety relays for emergency stop, guard door and light curtain monitoring

Off-delayed

1)

24

V DC

Cat.4according toEN954-1

PLeaccording to EN ISO13849-1

SILCL3according to IEC62061

SIL3according to IEC61508

SIL3only forhighdemand

requirements

2

2

0

ESR5-NV3-30

118705

Two-hand relay, suitable for applications to EN 574 Typ III C

dual channel

24

V DC, 24 V AC,

50/60

Hz

Cat.4according toEN954-1

PLeaccording toEN ISO13849-1

SILCL3according to IEC62061

SIL3according to IEC61508

2

1

ESR5-NZ-21-24VAC-DC

118703

1

off

Contact expansion modules

The basic device determines the maximum stop category according to IEC 61508 and IEC 60204

Off-delayed

24

V DC, 24 V AC,

50/60

Hz

Cat.3according toEN954-1

PLdaccording toEN ISO13849-1

SILCL2according to IEC62061

SIL2according to IEC61508

4

2

ESR5-VE3-42

118706

Non-delayed

24

V DC, 24 V AC,

50/60

Hz

Cat.4according toEN954-1

PLeaccording toEN ISO13849-1

SILCL3according to IEC62061

SIL3according to IEC61508

5

2

ESR5-NE-51-24VAC-DC

118707

1

off

Notes

1)

Suitable for safety position switch with

guard locking LS-S…MT-ZBZ.

Information relevant for export to North America

Product Standards IEC/EN see Technical Data; UL 508; CSA-C22.2 No. 14-95; CE marking

UL File No.

E29184

UL CCN

NKCR; NKCR7

CSA File No.

UL report applies to both US and Canada

CSA Class No.

3211-83; 3211-03

NA Certification

UL Listed, certified by UL for use in Canada

Degree of Protection IEC: IP20, UL/CSA Type: -

HPL13015EN