Background Image
Table of Contents Table of Contents
Previous Page  50 / 439 Next Page
Information
Show Menu
Previous Page 50 / 439 Next Page
Page Background

5/46

Illumination contactors

Switchgear for illumination systems

2010

CA08103002Z-EN

www.eaton.com

Switchgear for illumination systems

Engineering

DIL

L12

L18

L20

M7

M9

M12

M17

M25

M32

M40

M50

Permissible compensation capacitance C

max

[

mF] 470

470

470

47

80

100

220

330

470

470

500

Filament bulbs

I

e

[

A]

14

21

27

6

7.5

10

14

21

27

33

42

Mercury blended lamps

I

e

[

A]

12

16

23

5

6.5

8.5

12

16

23

30

38

Fluorescent lamps, conventional reactor –

starter – connection

I

e

[

A]

20

26

35

9

10

15

20

26

35

41

45

Fluorescent lamps, duo circuit (series

compensated)

I

e

[

A]

20

26

35

5.5

8

13

15

22.5

29

36

47

Electronic upstream devices

I

e

[

A]

12

18

20

5

6.5

8.5

12

17.5

22.5

28

35

High-pressure mercury vapour lamps I

e

[

A]

12

18

20

3.5

6

10

12

17.5

20

25

30

Metal-halide lamps

I

e

[

A]

12

18

20

3.5

6

10

12

17.5

20

25

30

High-pressure sodium lamps

I

e

[

A]

12

18

20

3.5

6

10

12

17.5

20

25

30

Low-pressure sodium lamps

I

e

[

A]

7.5

10

12

3

4

6

7.5

10

12

15

22

DIL

M65 M80

M95

M115 M150 M185A M225A M250

M300A M400

M500

Permissible compensation capacitance C

max

[

mF] 500

550

620

830

970

2055

2300

2600

3000

3250

3500

Filament bulbs

I

e

[

A]

55

67

79

95

125

153

187

208

249

332

415

Mercury blended lamps

I

e

[

A]

45

65

67

80

110

123

150

167

200

266

332

Fluorescent lamps, conventional reactor –

starter – connection

I

e

[

A]

55

95

100

125

145

207

237

263

300

375

525

Fluorescent lamps, duo circuit (series

compensated)

I

e

[

A]

59

71

95

100

138

186

213

236

270

338

473

Electronic upstream devices

I

e

[

A]

45.5

56

66.5

80.5

105

130

158

175

210

280

350

High-pressure mercury vapour lamps I

e

[

A]

36

55

60

80

95

138

158

175

200

250

350

Metal-halide lamps

I

e

[

A]

36

55

60

80

95

138

158

175

200

250

350

High-pressure sodium lamps

I

e

[

A]

36

55

60

80

95

138

158

175

200

250

350

Low-pressure sodium lamps

I

e

[

A]

25

35

40

50

70

100

111

123

140

175

245

In compensated lamps, the sum of the capacitances must not exceed the contactors' max. permissible capacitor load (C

max

)!

The values in the table are for each individual contactor contact.

DILL...