7/50
Motor-protective circuit-breakers PKZ2
Compact starters, high-capacity compact starters
2010
CA08103002Z-EN
www.eaton.comCompactstarters,high-capacitycompactstarters
Max. motor rating
Rateduninterrupted
current
Setting range
AC-3
I
u
Overload releases Short-circuit releases
220
V 230 V
240
V
380
V 400 V
415
V
440
V
500
V
660
V 690 V A
I
r
I
rm
P
P
P
P
P
A
A
kW
kW
kW
kW
kW
Compact starters, type “1” coordination
0.12
0.25
0.25
0.37
0.55
1
0.6…1
8…14
0.25
0.55
0.55
0.75
1.1
1.6
1…1.6
14…22
0.37
0.75
1.1
1.1
1.5
2.4
1.6…2.4
20…35
0.75
1.5
1.5
2.2
3
4
2.4…4
35…55
1.1
2.2
3
3
4
6
4…6
50…80
2.2
4
4
5.5
7.5
10
6…10
80…140
4
7.5
9
9
12.5
16
10…16
130…220
5.5
12.5
12.5
15
22
25
16…25
200…350
7.5
15
17.5
22
22
32
24…32
275…425
11
18.5
22
24
30
36
32…40
350…500
High-capacity compact starters, type “2” coordination
0.12
0.25
0.25
0.37
0.55
1
0.6…1
8…14
0.25
0.55
0.55
0.75
1.1
1.6
1…1.6
14…22
0.37
0.75
1.1
1.1
1.5
2.4
1.6…2.4
20…35
0.75
1.5
1.5
2.2
3
4
2.4…4
35…55
1.1
2.2
3
3
4
6
4…6
50…80
2.2
4
4
5.5
7.5
10
6…10
80…140
4
7.5
9
9
12.5
16
10…16
130…220
5.5
12.5
12.5
15
22
25
16…25
200…350
7.5
15
17.5
22
22
32
24…32
275…425
11
18.5
22
24
30
36
32…40
350…500
Notes
Information relevant for export to North America
Product Standards
IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No.
E36332
UL CCN
NLRV
CSA File No.
012528
CSA Class No.
3211-05
NA Certification
UL Listed, CSA certified
Suitable for
Branch circuit: as manual controller with contactor, suitable for group installations
See also
→Page 7/75
L
A1 13 21
14 22
A2
T
Ι >
L
A1 13 21
14 22
A2
T
I
>>
I
>