Background Image
Table of Contents Table of Contents
Previous Page  240 / 439 Next Page
Information
Show Menu
Previous Page 240 / 439 Next Page
Page Background

7/48

Motor-protective circuit-breakers PKZ2

Motor-protective circuit-breakers, circuit-breaker

2010

CA08103002Z-EN

www.eaton.com

Motor-protectivecircuit-breakers,circuit-breaker

Ordering

Max. motor rating

Rated uninterrupted

current

Setting range

AC-3

I

u

Overload releases Short-circuit releases

220

V 230 V

240

V

380

V 400 V

415

V

440

V

500

V

690

V

A

I

r

I

rm

P

P

P

P

P

A

A

kW

kW

kW

kW

kW

Motor-protective circuit-breakers, type of coordination “1” and “2”

0.09

0.12

0.18

0.25

0.25

0.6

0.4…0.6

5 …8

0.12

0.25

0.25

0.37

0.55

1

0.6…1

8 …14

0.25

0.55

0.55

0.75

1.1

1.6

1…1.6

14 …22

0.37

0.75

1.1

1.1

1.5

2.4

1.6…2.4

20 …35

0.75

1.5

1.5

2.2

3

4

2.4…4

35 …55

1.1

2.2

3

3

4

6

4…6

50 …80

2.2

4

4

5.5

7.5

10

6…10

80 …140

4

7.5

9

9

12.5

16

10…16

130 …220

5.5

12.5

12.5

15

22

25

16…25

200 …350

7.5

15

17.5

22

22

32

24…32

275 …425

11

20

22

24

30

40

32…40

350 …500

Circuit-breakers

For line and cable protection

–

–

–

–

–

10

6…10

50 …80

–

–

–

–

–

16

10…16

80 …140

–

–

–

–

–

25

16…25

130 …210

–

–

–

–

–

32

24…32

160 …280

–

–

–

–

–

40

32…40

200 …350

Notes

Information relevant for export to North America

Product Standards

UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking

UL File No.

E36332

UL CCN

NLRV

CSA File No.

12528

CSA Class No.

3211-05

NA Certification

UL Listed, CSA certified

Suitable for

Branch circuit: as manual controller suitable for group installations

See also

→Page 7/75

I

>

I

>

PKZ2