7/48
Motor-protective circuit-breakers PKZ2
Motor-protective circuit-breakers, circuit-breaker
2010
CA08103002Z-EN
www.eaton.comMotor-protectivecircuit-breakers,circuit-breaker
Ordering
Max. motor rating
Rated uninterrupted
current
Setting range
AC-3
I
u
Overload releases Short-circuit releases
220
V 230 V
240
V
380
V 400 V
415
V
440
V
500
V
690
V
A
I
r
I
rm
P
P
P
P
P
A
A
kW
kW
kW
kW
kW
Motor-protective circuit-breakers, type of coordination “1” and “2”
0.09
0.12
0.18
0.25
0.25
0.6
0.4…0.6
5 …8
0.12
0.25
0.25
0.37
0.55
1
0.6…1
8 …14
0.25
0.55
0.55
0.75
1.1
1.6
1…1.6
14 …22
0.37
0.75
1.1
1.1
1.5
2.4
1.6…2.4
20 …35
0.75
1.5
1.5
2.2
3
4
2.4…4
35 …55
1.1
2.2
3
3
4
6
4…6
50 …80
2.2
4
4
5.5
7.5
10
6…10
80 …140
4
7.5
9
9
12.5
16
10…16
130 …220
5.5
12.5
12.5
15
22
25
16…25
200 …350
7.5
15
17.5
22
22
32
24…32
275 …425
11
20
22
24
30
40
32…40
350 …500
Circuit-breakers
For line and cable protection
–
–
–
–
–
10
6…10
50 …80
–
–
–
–
–
16
10…16
80 …140
–
–
–
–
–
25
16…25
130 …210
–
–
–
–
–
32
24…32
160 …280
–
–
–
–
–
40
32…40
200 …350
Notes
Information relevant for export to North America
Product Standards
UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
UL File No.
E36332
UL CCN
NLRV
CSA File No.
12528
CSA Class No.
3211-05
NA Certification
UL Listed, CSA certified
Suitable for
Branch circuit: as manual controller suitable for group installations
See also
→Page 7/75
I
>
I
>
PKZ2