6/8
Overload relays
Overload relays up to 150A
2010
CA08103002Z-EN
www.eaton.comOverload relaysup to 150A
Overload relaysup to 150A
Setting range of
overload releases
Circuit symbol
Auxiliary contact
For use with
Short-circuit protection
N/O=normallyopencontact
NC=normallyclosedcontact
Contactors
Soft starters
Type “1”
coordination
Type “2”
coordination
I
r
gG/gL
gG/gL
A
A
A
ZB12 overload relay
0.1 – 0.16
1
N/O 1 NC
DILM7, DILM9,
DILM12, DILM15,
DIULM7, DIULM9,
DIULM12,
SDAINLM12,
SDAINLM16,
SDAINLM22
–
25
0.5
0.16 – 0.24
1
0.24 – 0.4
2
0.4 – 0.6
4
0.6 – 1
4
1 – 1.6
6
1.6 – 2.4
10
2.4 – 4
DS7-34…SX004…
16
4 – 6
DS7-34…SX005…
20
6 – 10
DS7-34…SX007…
DS7-34…SX009…
50
25
9 – 12
DS7-34…SX012…
12 – 16
–
ZB32 overload relay
0.1 – 0.16
1
N/O 1 NC
DILM17, DILM25,
DILM32,
DILM38,
DILMF8,
DILMF11,
DILMF14,
DILMF17,
DILMF25,
DILMF32,
DIULM17,
DIULM25,
DIULM32,
SDAINLM30,
SDAINLM45,
SDAINLM55
–
25
0.5
0.16 – 0.24
1
0.24 – 0.4
2
0.4 – 0.6
4
0.6 – 1
4
1 – 1.6
6
1.6 – 2.4
10
2.4 – 4
16
4 – 6
20
6 – 10
50
25
10 – 16
DS7-34...SX016...
63
35
16 – 24
DS7-34...SX024...
100
35
24 – 32
DS7-34...SX032...
125
63
32 – 38
–
125
63
Information relevant for export to North America
Product Standards UL 508; CSA-C22.2 No. 14; IEC/EN
60947-4-1;
CE marking
UL File No.
E29184
UL CCN
NKCR
CSA File No.
12528
CSA Class No.
3211-03
NA Certification
UL Listed, CSA certified
Suitable for
Branch circuits
Max. voltage R
Rating
600
V AC
Degree of Protection IEC: IP20, UL/CSA Type: -
See also
→Page 6/29
2 4 6 98 96
A2 14/
22
97 95
2 4 6 98 96 14/
22
97 95
ZB12, ZB32
HPL06008EN