Background Image
Table of Contents Table of Contents
Previous Page  72 / 91 Next Page
Information
Show Menu
Previous Page 72 / 91 Next Page
Page Background

TECHNI CAL DATA

G MCCB

72

56.4

44.6

29.5

21.6

17.7

Ø5.1

Ø6.0

.98 [24.9]

15-30A= 12.4

30-125A= 9.4

25.0

50.1

75.1

88.9

88.9

136.4

121.2

99.6

56.4

ON

TRIP

OFF

RESET

FROM THE 5 SEC VALUE FOR THE 125A BREAKER,

THE ABOVE CURVE SUGGESTS A OHMIC VALUE OF 0.33 OHMS

I

0.4 SEC VALUES

Ampere 15 20 25 30 40 50 60 80 100 125

Ohm 1.18 0.88 0.71 0.59 0.44 0.35 0.29 0.27 0.22 0.2

5 SEC VALUES (230V / 5.5X IN) FOR OTHER RATINGS ARE AS FOLLOWS

Ampere 15 20 25 30 40 50 60 80 100 125

Ohm 2.79 2.09 1.67 1.39 1.05 0.84 0.70 0.52 0.42 0.33

GG FRAME MCCBs TECHNICAL SPECIFICATION

l

GG FRAME SPECIFICATION

I

• Specification IEC 60947-2

• Current Range 15 – 125A

• Ue Rated Operation Voltage 240V SP 415V TP

• Ui Rated Insulation Voltage 500V AC

• Rated Frequency 50/60Hz

• Release Thermal Magnetic

• Adjustment None

• Ambient Range -20°C to 55°C

• Humidity Range 0 – 90%

• Weight SP - 0.4kg TP - 0.95kg

• Mechanical Duration 8000 operations

SUMMARY

I

The Powerstar GG frame breaker is a compact, robust design that is suitable

for panel or DIN rail mounting without the need for additional adapters.

Accessories including auxiliary releases and contacts are available upon

request.

AVAILABLE OPTIONS

I

• Padlocking

• AUX switches

SHORT CIRCUIT BREAKING CAPACITY

I

Type

Ue Icu

TP

220 V 30

415 V 25

Ics

= 50% Icu

MAIN CONNECTIONS

I

Clamps:

30A = 16mm

2

30A = 50mm

2