Background Image
Table of Contents Table of Contents
Previous Page  74 / 91 Next Page
Information
Show Menu
Previous Page 74 / 91 Next Page
Page Background

TECHNI CAL DATA

J MCCB

74

7T2 FRAME MCCBs TECHNICAL SPECIFICATION

l

7T2 FRAME SPECIFICATION

I

• Specification IEC 60947-2 & IEC 60947-3

• Current Range 40 – 250A

• Ue Rated Operation Voltage 690V AC

• Ui Rated Insulation Voltage 690V AC

• Rated Frequency 50/60Hz

• Release Electronic

• Thermal Adjustment 0.4 – 1.0 x Trip Unit

Rated Current

• Instantaneous Adjustment Adjustable

• Icu (415V) Short Circuit Breaking Capacity 7T2S 36kA 7T2H 65kA

• Ambient Range -40°C to 55°C

• Working Environment Both Dry and Tropical

Climates

• Mechanical Endurance 30,000 Cycles

7T2 FRAME FEATURES

I

The 7T2 circuit breaker consists of a switching unit and either a range of

different rated electronic trip units or a switch disconnector module. The

modular design provides the maximum flexibilty as the user can decide not

only the rating but also the function, disconnector or protective device. With

a wide setting bandwidth electronic trip units offer unparalled functionality.

AVAILABLE OPTIONS

I

• ST UVR

• Aux SW

• Rotary Handle (available on request)

• Padlocking

• Terminal Shrouds

(See Product Section for selection)

SHORT CIRCUIT BREAKING CAPACITY

I

Ue 7T2S Icu 7T2H Icu

280 V 60 kA 100kA

415 V 36kA 65kA

Ics

= 50% Icu

TRIP UNIT SETTINGS

I

Over current

I

R = 0 x 4 - 1.0 x

I

n

Instantaneous 4 or 8 x

I

R

I

n - Nominal Trip Unit Rating

MAIN CONNECTIONS

I

Front-connected clamps –

150mm

2

AUXILIARY EQUIPMENT OPTIONS (RETRO-FITTABLE)

I

a) UVR

b) Shunt Trip

c) Auxiliary Switches

Shunt Trip Voltage Range 70%

Under Voltage Release Threshold 35%

Input Power of Auxiliary Releases < 3VA AC, < 3W DC

CURRENT CHARACTERISTICS

I

IR & II SET AT MINIMUM

CURRENT VALUE (A)

OHMIC VALUE

0.4

5

0.4

5

AMPS SECONDS SECONDS VOLTAGE SECONDS SECONDS

100

150A

150A

230V 1.533

Ω

1.533

Ω

160

240A

240A

230V 0.958

Ω

0.958

Ω

250

375A

375A

230V 0.613

Ω

0.613

Ω

IR SET AT MINIMUM & II SET AT MAXIMUM

100

320A

230A

230V 0.719

Ω

1.000

Ω

160

512A

368A

230V 0.449

Ω

0.625

Ω

250

800A

575A

230V 0.288

Ω

0.400

Ω

IR & II SET AT MAXIMUM

100

800A

600A

230V 0.288

Ω

0.383

Ω

160

1280A 960A

230V 0.180

Ω

0.240

Ω

250

2000A 1500A 230V 0.115

Ω

0.153

Ω

IR SET AT MAXIMUM & II SET AT MINIMUM

100

400A

400A

230V 0.575

Ω

0.575

Ω

160

640A

640A

230V 0.359

Ω

0.359

Ω

250

1000A 1000A 230V 0.230

Ω

0.230

Ω

100 ... 150

100 ... 150