TECHNI CAL DATA
J MCCB
74
7T2 FRAME MCCBs TECHNICAL SPECIFICATION
l
7T2 FRAME SPECIFICATION
I
• Specification IEC 60947-2 & IEC 60947-3
• Current Range 40 – 250A
• Ue Rated Operation Voltage 690V AC
• Ui Rated Insulation Voltage 690V AC
• Rated Frequency 50/60Hz
• Release Electronic
• Thermal Adjustment 0.4 – 1.0 x Trip Unit
Rated Current
• Instantaneous Adjustment Adjustable
• Icu (415V) Short Circuit Breaking Capacity 7T2S 36kA 7T2H 65kA
• Ambient Range -40°C to 55°C
• Working Environment Both Dry and Tropical
Climates
• Mechanical Endurance 30,000 Cycles
7T2 FRAME FEATURES
I
The 7T2 circuit breaker consists of a switching unit and either a range of
different rated electronic trip units or a switch disconnector module. The
modular design provides the maximum flexibilty as the user can decide not
only the rating but also the function, disconnector or protective device. With
a wide setting bandwidth electronic trip units offer unparalled functionality.
AVAILABLE OPTIONS
I
• ST UVR
• Aux SW
• Rotary Handle (available on request)
• Padlocking
• Terminal Shrouds
(See Product Section for selection)
SHORT CIRCUIT BREAKING CAPACITY
I
Ue 7T2S Icu 7T2H Icu
280 V 60 kA 100kA
415 V 36kA 65kA
Ics
= 50% Icu
TRIP UNIT SETTINGS
I
Over current
I
R = 0 x 4 - 1.0 x
I
n
Instantaneous 4 or 8 x
I
R
I
n - Nominal Trip Unit Rating
MAIN CONNECTIONS
I
Front-connected clamps –
150mm
2
AUXILIARY EQUIPMENT OPTIONS (RETRO-FITTABLE)
I
a) UVR
b) Shunt Trip
c) Auxiliary Switches
Shunt Trip Voltage Range 70%
Under Voltage Release Threshold 35%
Input Power of Auxiliary Releases < 3VA AC, < 3W DC
CURRENT CHARACTERISTICS
I
IR & II SET AT MINIMUM
CURRENT VALUE (A)
OHMIC VALUE
0.4
5
0.4
5
AMPS SECONDS SECONDS VOLTAGE SECONDS SECONDS
100
150A
150A
230V 1.533
Ω
1.533
Ω
160
240A
240A
230V 0.958
Ω
0.958
Ω
250
375A
375A
230V 0.613
Ω
0.613
Ω
IR SET AT MINIMUM & II SET AT MAXIMUM
100
320A
230A
230V 0.719
Ω
1.000
Ω
160
512A
368A
230V 0.449
Ω
0.625
Ω
250
800A
575A
230V 0.288
Ω
0.400
Ω
IR & II SET AT MAXIMUM
100
800A
600A
230V 0.288
Ω
0.383
Ω
160
1280A 960A
230V 0.180
Ω
0.240
Ω
250
2000A 1500A 230V 0.115
Ω
0.153
Ω
IR SET AT MAXIMUM & II SET AT MINIMUM
100
400A
400A
230V 0.575
Ω
0.575
Ω
160
640A
640A
230V 0.359
Ω
0.359
Ω
250
1000A 1000A 230V 0.230
Ω
0.230
Ω
100 ... 150