Background Image
Table of Contents Table of Contents
Previous Page  182 / 211 Next Page
Information
Show Menu
Previous Page 182 / 211 Next Page
Page Background

182

TECHN I CAL DATA

1 7 t h ED I T I ON COMP L I ANCE

MAINS SUPPLIES FOR SMOKE ALARMS

WITHIN DOMESTIC SETTINGS

Clause 7.1 of BS 5839-6 defines a Grade D system

as: “A system

of one or more mains-powered smoke alarms, each with an integral

standby supply (The system may in addition, incorporate one or more

mains-powered heat alarms each with an integral standby supply).

The 17th Edition of the wiring regulations do not cover every item of

Electrical Equipment likely to be installed. They do not specifically

mention Smoke Alarms. However:

CHAPTER 13 REGULATION 134.1.1

states that electrical equipment

shall be installed in accordance with the instructions of the

manufacturer of the equipment.

CHAPTER 51 REGULATION 510.2

states that every item of electrical

equipment shall be selected and erected so as to allow compliance

with the regulations stated in this chapter and the relevant regulations

in other parts of BS7671 and shall take account of manufacturers

instructions.

Elements of Electrical Protection will include short circuit, overcurrent

and may also include additional protection by a residual current device

(30mA) for certain installation methods covered by BS7671 (522.6.7)

& (522.6.8)

IF ADDITIONAL PROTECTION IS REQUIRED BY BS7671 THE NEED

FOR SEPARATE ELECTRICAL PROTECTION CANNOT BE MET BY

DUAL RCD CONSUMER UNIT ARRANGEMENTS WHERE SINGLE

RESIDUAL CURRENT DEVICES PROTECT GROUPS OF CIRCUITS.

REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.

l

SOCKET CIRCUITS 411.3.3

RCDs are now required to provide additional protection. To be recognised

as providing additional protection the RCD must be rated at 30mA or less

and operate within 40ms when tested at 5x rated residual operating current.

RCDs are now required for all general use socket outlets

rated up to 20A.

Two exceptions are allowed for ;

1.

Socket outlets used under supervision of skilled or instructed persons.

2.

A socket outlet suitably identified for connection of a particular

item of equipment.

Additional protection must be provided in the event of failure of the

provision of basic protection and/or the provision of fault protection or

carelessness by users of the installation.

Protection by 30mA RCD will

be required for;

Upstairs ring circuit

Downstairs ring circuit

Kitchen ring circuit

Cooker control unit c/w socket outlet

CABLES 522.6.6 522.6.7 522.6.8

Regulation 522.6.6

A cable concealed in a wall or partition at less than 50mm from the

surface shall;

1.

Incorporate an earthed metallic covering suitable for service as the

circuit CPC -

or

2.

Be enclosed in earthed conduit

or

3.

Be enclosed in trunking or ducting

or

4.

Be mechanically protected against damage from penetration by nails

or screws and the like

or

5.

Be installed in the prescribed zones.

Regulation 522.6.7

Where 522.6.6 applies and the installation is

not

intended to be under the supervision of skilled or instructed

persons,

cables installed in accordance with 522.6.6(5) but not having

mechanical protection of 1,2,3 or 4 shall be provided with additional

protection by means of a 30mA RCD.

In the majority of domestic situations cables installed beneath a plaster

surface within partition walls without mechanical protection will require

additional protection by

30mA RCD regardless

of their routing.

Upstairs lighting

Downstairs lighting

Immersion heater

Smoke alarm

Burglar alarm

Bathrooms

Section 7

Special installations or Locations.

Section 701

Locations containing a bath or shower.

Zone 3 has been removed.

Suitable equipment can be within 600mm of a bath, excluding 13A

sockets to BS1363 which must be 3m from the edge of a bath or

shower.

Additional protection shall be provided by the use of

one or more

residual current device

with a rated operating current not

exceeding 30mA (701.411.3.3).

Supplementary bonding is not required so long as any Protective

Equipotential Bonding has been installed (411.3.1.2).

Additional protection must be provided by one or more 30mA RCDs.

shower circuit

lighting circuit

Heating circuit

Ventilation circuit

Chapter 31

314.1 Requires that; Every installation shall be divided into circuits,

as necessary, to:

i.

Avoid danger and minimise inconvenience in the event of a fault

ii.

Facilitate safe inspection, testing and maintenance

iii.

Take account of danger that may arise from the failure of a single

circuit such as a lighting circuit

iv.

Reduce the possibility of unwanted tripping of residual current

devices (RCDs) due to excessive protection conductor currents

produced by equipment in normal operation.

British Standards and IEE regulations are subject to change and

amendment. This guide to Crabtree consumer units is not a

substitute for the regulations which should always be used for

all types of electrical installation design, and installation work.

Manufacturers

Instructions

BS7671

BS5839-6

Installation shall be in

accordance with

BS 7671 & BS5839-6

522.6.7

522.6.8

560.7.1

cable installation

method

Clause 15.5 states that

Grade D systems can be

wired from either:

A. An independent

circuit at the dwellings

main distribution board.

B. A separately

electrically protected

regularly used lighting

circuit.

Main

Switch

RCD

MCB

MCB

MCB

MCB

MCB

MCB

RCD

SD

SD

MCB or RCBO

MCB or RCBO

Main

Switch

RCD

MCB or RCBO

MCB or RCBO

MCB

MCB

MCB

MCB

MCB

MCB

RCD

SD

SD

SD

A.

B.