EMEX Test

System components

27

MXC substation

The MXC substation controls up to 40 LTC

equipped HF luminaires. It can also monitor 8 switched

or unswitched inputs.

l

40 x LTC units over 2 radials (20 per radial)

l

Maximum 270V AC

l

2 x 1,150VA (5 ampere) maximum output power

l

200 metres maximum distance (per output radial)

to final luminaire

l

2-core screened 240V, (1.0mm

2

minimum) cable (fireproof recommended)

l

210mm x 253mm x 60mm

l

Operating temperature 0 – 50°C

l

Galvanised steel enclosure (colour options available as specials)

l

Substation rated to IP2x as standard. Option of higher IP rating available to order

l

For further details on the MXC & MXD please refer to the

MXD4 4-way addressable substation

The MXD4 addressable substation controls up to 4 unmodified mains

luminaires. It can also monitor 8 switched and/or 8 unswitched inputs.

l

4 luminaires on individual circuits

l

Maximum 270V AC, 230W (1 ampere per circuit)

l

Switching threshold of 230V -60% to -85%

l

Address range of 4 to 3999 (blocks of 4)

l

Analogue and digital compatible dimming capability using on-board

dimming relay to break dimmer control line

l

2-core screened 240V, (1.0mm2 minimum) cable (fireproof

recommended)

l

2,500 metres maximum distance from MXKP to MXD4 transmitter

l

254mm x 210mm x 60mm

l

Operating temperature 0 – 50°C

l

Galvanised steel enclosure (colour options available as specials)

l

Substation rated to IP2x as standard. Option of higher IP rating

available to order

MXT data repeaters

MXT100

MXT200

The MXT data repeater is used to increase the number of interfaces on an

individual data line.

l

Maximum 270V AC

l

2-core data inputs

l

2-core screened 240V, (1.0mm2 minimum) cable (fireproof recommended)

l

300mm x 400mm x 120mm

Up to 100 substations may be fed from the internal transmitter within the CPS. Additional MXT data repeaters are

available for situations where more than 100 substations are required. For example the MXT200 data repeater is