5/44

Processing capacities of Modicon platforms

Processing capacity

The table below can be used to compare, for each station, the total number of

messages received via the Modbus (or Uni-TE) messaging service, if used, (value

R1, R2 or Ri) with the capacity of the station processor.

Processing of Modbus requests per PLC scan cycle

Modicon M340, Modicon Premium platforms

Messages received

Total messages received by the

PLC from all the communication

modules

(1)

TSX P57 10

4

messages/cycle

BMX P34 20 / TSX P57 20

8

messages/cycle

TSX P57 30

12

messages/cycle

TSX P57 40

16

messages/cycle

TSX P57 50/60

(2)

16/20

messages/cycle

Modicon

Quantum

platform

Integrated port limitations Communication module

limitations

Ethernet

modules

per PLC

All types of

communication

request

Additional

read/write 4x

registers

All types of

communication

request

Additional

read/write 4x

registers

140

CPU 113

(3)

1

message/

cycle

4

messages/

cycle

2

max.

140

CPU 311

1

message/

cycle

4

messages/

cycle

2

max.

140

CPU 434

140

CPU 534

(3)

4

messages/

cycle

8

messages/

cycle

6

max.

140

CPU 651

16

messages/

cycle

16

messages/

cycle

4

messages/

cycle

8

messages/

cycle

6

max.

Messages/cycle:

number of messages received per scan cycle from the PLC master task

(

typical cycle of 50 to 100 ms)

Example:

Modicon Quantum

140

CPU 434 12

p

processor with 4 Ethernet

140

NOE 771

p

1

modules:

- 20

messages/cycle for all types of communication request, and

- 32

messages/cycle for the read/write 4x registers

Ethernet transaction processing capacity

For each station, compare the total number of messages received

[

values Ri, Rj]

and the total number of messages transmitted

[

values Ei, Ej] (for station N, for

example) with the Ethernet transaction processing capacity shown below.

Use the following elements for the Ethernet connection per PLC, rather than the

number of transactions required by the application.

Ethernet transaction

processing capacity

Modicon M340 BMX

Modicon Premium TSX

Modicon Quantum 140

NOE 0100

NOE 0110

NOC 0401

NOR 0200H

P34 2020

P34 20302

ETY 110WS ETY 4103/5103

WMY 100

ETC 101

P57 10...40

P57 50

P57 60

NOE 771 00/10

NOE 771 01/11

NWM 100 00

NOC 771 01

CPU 651 50/60

CPU 652 60

Modbus messaging

500

transactions/s

500

transactions/s

60

transactions/s 450

transactions/s

500

transactions/s

350

transactions/s

350

transactions/s

I/O Scanning service

2,000

transactions/s

Server mode

(4)

Service not

available

2,000

transactions/s

(5)

2,000

transactions/s

2,000

transactions/s

(5)

2,000

transactions/s

Global Data

subscription

800

Service not

available

Service not

available

800

(6)

800

800

(6)

800

(1)

A temporary overload, due for example to an adjustment terminal or the temporary connection

of an Internet browser, lasting for a few PLC scans, is permissible.

(2)

Only with Unity Pro software.

(3)

Only with Concept/ProWORX software.

(4)

BMX P34 20

ppp

processors with Modbus TCPmessaging in server mode can be scanned by

a device that has the I/O Scanning service.

(5)

TSX WMY 100

and

140

NWM 100 00

modules do not have the I/O Scanning service.

(6)

TSX WMY 100, TSX ETC 101, 140 NWM 100 00

and

140

NOC 771 01

modules do not have

the Global Data service.

Performance

(

continued)

Modicon Premium automation

platform

Ethernet Modbus/TCP network

Performance

2

1

3

4

5

6

7

8

9

10