8

Trip unit summary table

Trip unit type

Digitrip 220

2)

Digitrip 520 i

Digitrip 520M i

Digitrip 520MC i

Digitrip 1150 i

3)

Ampere range

200

A - 3200 A

200

A - 6300 A

200

A - 6300 A

200

A - 6300 A

200

A - 6300 A

Interrupting rating at 690 V

40

through 100 kA

40

through 100 kA

40

through 100 kA

40

through 100 kA

40

through 100 kA

Rms sensing

Yes

Yes

Yes

Yes

Yes

Protection and coordination

Protection

Ordering options

LI

LSI, LSIG

LSI, LSIG, LSIA

LSI, LSIG, LSIA

LSI, LSIG, LSIA

Fixed rate plug (I

n

)

Yes

Yes

Yes

Yes

Yes

Overtemperature trip

Yes

Yes

Yes

Yes

Yes

Long

Long delay pickup

1.0

x (I

n

)

Fixed

2)

0.4 - 1.0

x (I

n

)

0.4 - 1.0

x (I

n

)

0.4 - 1.0

x (I

n

)

0.4 - 1.0

x (I

n

)

delay

Long delay time I

2

t at 6 x I

r

10

seconds

2)

2 - 24

seconds

2 - 24

seconds

2 - 24

seconds

2 - 24

seconds

protection

Long delay time I

4

t

No

No

No

No

1 - 5

seconds

(

L)

Long delay thermal memory

Yes

Yes

Yes

Yes

Yes

High load alarm

No

No

No

No

0.5 - 1.0

x (I

r

)

Short

Short delay pickup

No

200 - 1000%

x (I

r

)

200 - 1000%

x (I

r

)

200 - 1000%

x (I

r

)

200 - 1000%

x (I

r

)

delay

and M1

and M1

and M1

and M1

protection

Short delay time I

2

t at 8 x I

r

No

100 - 500

ms

100 - 500

ms

100 - 500

ms

100 - 500

ms

(

S)

Short delay time flat

No

100 - 500

ms

100 - 500

ms

100 - 500

ms

100 - 500

ms

Short delay time ZSI

No

Yes

Yes

Yes

Yes

Instantaneous

Instantaneous pickup

200 - 1000%

x ( I

n

)

200 - 1000%

x (I

n

)

200 - 1000%

x (I

n

)

200 - 1000%

x (I

n

)

200 - 1000%

x (I

n

)

protection

and M1

and M1

and M1

and M1

(

I)

Making current release

Yes

Yes

Yes

Yes

Yes

Off position

No

Yes

Yes

Yes

Yes

Earth fault

Earth fault alarm

No

No

Yes

Yes

Yes

protection

Earth fault pickup

No

25 - 100%

x (I

n

)

25 - 100%

x (I

n

)

25 - 100%

x (I

n

)

24 - 100%

x (I

n

)

(

G)

Earth fault delay I

2

t at .625 x I

n

No

100 - 500

ms

100 - 500

ms

100 - 500

ms

100 - 500

ms

Earth fault delay flat

No

100 - 500

ms

100 - 500

ms

100 - 500

ms

100 - 500

ms

Earth fault ZSI

No

Yes

Yes

Yes

Yes

Earth fault thermal memory

No

Yes

Yes

Yes

Yes

Neutral protection (N)

Yes

Model LSI only

Model LSI only

Model LSI only

Model LSI only

System diagnostics

Cause of trip LEDs

No

2)

Yes

Yes

Yes

Yes

Magnitude of trip information

No

No

No

Yes

Yes

Remote signal contacts

No

No

Yes

Yes

Yes

Programmable contacts

No

No

No

No

Yes

System monitoring

Digital display

No

No

4

char. LCD

4

char. LCD

24

char. LED

Current (%) full scale sensor

No

No

Yes

Yes

Yes +/- 1%

Voltage (%) L - L

No

No

No

No

Yes

Power and energy (%)

No

No

No

No

Yes

Apparent power kVA and demand

No

No

No

No

Yes

Reactive power kVAR

No

No

No

No

Yes

Power factor

No

No

No

No

Yes

Crest factor

No

No

No

No

Yes

Power quality - harmonics

No

No

No

No

Yes

%

THD

No

No

No

No

Yes

System communications

Type

No

No

No

INCOM/PowerNet

INCOM/PowerNet/

Trip Link

Power supply

N/A

N/A

PRM in breaker

PRM in breaker

PRM in breaker

3)

Additional features

Trip log (3 events)

No

No

No

No

Yes

Electronic operations counter

No

No

No

No

Yes

Testing method

1)

Test set

Test set

Test set

Test set

Integral and test set

Waveform capture

No

No

No

No

Yes

I

n

= Rating plug and sensor rating; I

r

= Long delay pickup setting.

1)

Test set for secondary injection.

2)

Long delay pickup will be adjustable from 0.4 - 1 x (I

n

).

Long delay time will be adjustable from 2 - 24 seconds. Cause of trip LEDs will be added with battery back up.

Contact Eaton for availability.

3)

New features will include over and under voltage alarm or trip, over and under frequency alarm or trip, voltage unbalance alarm or trip, and reverse power trip and

phase rotation alarm. Contact Eaton for availability and more details.

Magnum Digitrip trip units

The next generation of proven Digitrip RMS

Trip Units is available exclusively on Magnum

Breakers. These true rms sensing trip units

provide accurate coordination with the

conductors and equipment the breaker is

designed to protect.