6

Safety is enhanced by the through-

the-door design that provides for three

breaker positions with the door

closed: connect, test, and disconnect.

Connect

Test

Disconnect

Viewable through-the-window

electrical accessories are

identically sized, yet keyed for

error-free mounting.

The auxiliary switch is an internal

accessory that provides remote

electrical indication of the breaker

status.

An electric motor automatically

charges the closing springs. In

absence of control power, the

springs can be manually charged.

Magnum modular

design allows customers

to mount accessories in

the field.

A common family of accessories for all frame sizes

We designed Magnum accessories to fit all frame sizes,

thus reducing inventory parts and the possible confusion

that can exist when various accessory sizes are required

for individual breaker frames.

Magnum through-the-window accessories are installed in

the right front of the breaker. The unique windows in the

breaker cover enable accessories to be quickly identified

by name and rating. Additional internal accessories

include an auxiliary switch, over-current trip switch

(

alarm), and electrical motor operator.

Accessories are plug-in units that snap in place, providing

for easy mounting and wiring to save both installation

time and cost. This feature facilitates accessory changes

by the installer or user personnel, eliminating the need

for manufacturer modification or outside service

companies.

Modular accessories are keyed for fast error-free

mounting in the field. For example, the spring release

unit can only be mounted in the centre cavity.

Convenient secondary contact placement facilitates

wiring and maintenance

Secondary wiring points are located in the top front

portion of each cell. A separate door can be used to

cover the contacts so an operator can safely access

them without opening the breaker compartment door.

Customer contact points are dedicated to the customer’s

interface, totally free and isolated from factory

connections.

The secondary terminals have standard finger-proof

hinged covers, providing safety by protecting against

accidental contact with live secondary contacts.

Covers are hinged for making connections and include a

small access hole for circuit testing using a probe. Each

secondary contact point is dedicated to a specific

function, allowing standardised wiring diagrams and true

electrical interchangeability of common size breakers.

Standard wiring points help improve quality while

reducing maintenance and inspection time for end

customers.