D-22

PE and PEN conductors

To determine the required

size of the PE conductor,

see page D-48.

Two possibilities:

either the equation indicated by standard IEC 60439-1 to obtain an optimised

value:

Example

Isc = 36 kA rms

C

the value of the phase-to-earth fault current = 60 % of the value

of the phase-to-phase fault current (standard IEC 60439-1 §8.2.4.2), i.e.:

36 x 0.6 = 21.6 kA

maximum time delay for the control unit: 0.5 s

k = 143 for copper conductors with PVC insulation.

The calculation is therefore:

The PE conductor must therefore be a 25 x 5 mm bar (= 125 mm

2

).

or the Schneider Electric table based on the standard.

To determine the required

size of the PEN conductor,

see page D-49.

b

v

v

v

b

S

PE

21600

2

x 0.5

143

106 8

mm

2

=

= --------------------

S

PE

I

2

t

k

------

=