![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0070.png)
A-16
Compact NS630b to NS1600
vertical mounting with cable
Toggle, rotary handle and motor mechanism
Circuit breakers
Mounting
Front connection with cables
650 150
400
DD383692.eps
Devices
Fixed device
Withdrawable device
NS630b/1000
NS1250/1600
NS630b/1000
NS1250/1600
Number of devices per row
1
1
1
1
No. of vertical modules
12
14
13
15
Mounting plates
03482
03482
03483
03483
Front plates
[No. of vertical modules]
upstream
03802
[2]
03804
[4]
03802
[2]
03804
[4]
with cut-out
03690or 03701
(1)
[7]
03691
[8]
03691
[8]
downstream
03803
[3]
03803
[3]
03803
[3]
03803
[3]
Mounting
Rear connectionwith cables
150
DD383694.eps
Devices
Fixed device
Withdrawable device
NS630b/1600
NS630b/1600
Number of devices per row
1
1
No. of vertical modules
10
11
Mounting plates
03482
03483
Front plates
[No. of vertical
modules]
with cut-out
03690or 03701
(1)
[7]
03691
[8]
downstream
03803
[3]
03803
[3]
(1)
For devices with toggle or rotary handle catalogue number 03690, with a motor mechanism catalogue number 03701.
Connection
Upstream on incomer
Devices
Fixed device
Withdrawable device
NS630b/1000
NS1250/1600
NS630b/1000
NS1250/1600
3P
4P
3P
4P
3P
4P
3P
4P
Type of terminals front connection Front connections supplied with the device
rear connection Vertical rear connections supplied with the device
Arc-chute cover
33596
33597
33596
33597
-
Vertical connection adapters
33642
(3)
33643
(3)
33642
(3)
33643
(3)
33642
(3)
33643
(3)
33642
(3)
33643
(3)
Cable-lug adapters
Direct
33644
(3)
33645
(3)
Direct
33644
(3)
33645
(3)
Spacing rods
-
04691
(3)
-
04691
(3)
Terminal extension bar support rear
connection
2 x
04693
Connection
must be made
(2)
on rear connection
Cables cover
front connection
04851
04852
rear connection
04853
(2)
Connection to be made according to the busbar drawings supplied by Schneider Electric.
(3)
Vertical connection adapters and cable-lug adapters are not compatible with input voltage
u
500 V.
Distribution
Downstream on Linergy LGY, LGYE or BS busbars
Dd383701.eps
Dd383702.eps
Devices
Fixed device
Withdrawable device
NS630b/1250
NS1600
NS630b/1250
NS1600
3P
4P
3P
4P
3P
4P
3P
4P
Type of terminals
Front connections supplied with the device
Busbars connection
For Linergy LGY busbars: prefabricated connection
04485
04486
04487
04488
04477
04478
04491
04492
Can be reversed for upstream supply
must be made
(4)
.
For Linergy LGYE and Linergy BS busbars
Free support for busbars connection
2 x
04662
Cover for busbars connection
04926
(4)
Connection to be made according to the busbar drawings supplied by Schneider Electric.
Note:
to make measurements:
b
install a Micrologic control unit capable of displaying the values.
b
or install the CTs on the horizontal busbars; in this case, an additional module is required; add a plain front plate downstream (03801).
Selection of Linergy LGY:
see page B-14,
Linergy LGYE:
see page B-15,
Linergy BS:
see page B-16.
Functional system
Functional units