Table of Contents Table of Contents
Previous Page  68 / 338 Next Page
Information
Show Menu
Previous Page 68 / 338 Next Page
Page Background

A-16

Compact NS630b to NS1600

vertical mounting with cable

Toggle, rotary handle and motor mechanism

Circuit breakers

Mounting

Front connection with cables

650 150

400

DD383692.eps

Devices

Fixed device

Withdrawable device

NS630b/1000

NS1250/1600

NS630b/1000

NS1250/1600

Number of devices per row

1

1

1

1

No. of vertical modules

12

14

13

15

Mounting plates

03482

03482

03483

03483

Front plates

[No. of vertical modules]

upstream

03802

[2]

03804

[4]

03802

[2]

03804

[4]

with cut-out

03690or 03701

(1)

[7]

03691

[8]

03691

[8]

downstream

03803

[3]

03803

[3]

03803

[3]

03803

[3]

Mounting

Rear connectionwith cables

150

DD383694.eps

Devices

Fixed device

Withdrawable device

NS630b/1600

NS630b/1600

Number of devices per row

1

1

No. of vertical modules

10

11

Mounting plates

03482

03483

Front plates

[No. of vertical

modules]

with cut-out

03690or 03701

(1)

[7]

03691

[8]

downstream

03803

[3]

03803

[3]

(1)

For devices with toggle or rotary handle catalogue number 03690, with a motor mechanism catalogue number 03701.

Connection

Upstream on incomer

Devices

Fixed device

Withdrawable device

NS630b/1000

NS1250/1600

NS630b/1000

NS1250/1600

3P

4P

3P

4P

3P

4P

3P

4P

Type of terminals front connection Front connections supplied with the device

rear connection Vertical rear connections supplied with the device

Arc-chute cover

33596

33597

33596

33597

-

Vertical connection adapters

33642

(3)

33643

(3)

33642

(3)

33643

(3)

33642

(3)

33643

(3)

33642

(3)

33643

(3)

Cable-lug adapters

Direct

33644

(3)

33645

(3)

Direct

33644

(3)

33645

(3)

Spacing rods

-

04691

(3)

-

04691

(3)

Terminal extension bar support rear

connection

2 x

04693

Connection

must be made

(2)

on rear connection

Cables cover

front connection

04851

04852

rear connection

04853

(2)

Connection to be made according to the busbar drawings supplied by Schneider Electric.

(3)

Vertical connection adapters and cable-lug adapters are not compatible with input voltage

u

500 V.

Distribution

Downstream on Linergy LGY, LGYE or BS busbars

Dd383701.eps

Dd383702.eps

Devices

Fixed device

Withdrawable device

NS630b/1250

NS1600

NS630b/1250

NS1600

3P

4P

3P

4P

3P

4P

3P

4P

Type of terminals

Front connections supplied with the device

Busbars connection

For Linergy LGY busbars: prefabricated connection

04485

04486

04487

04488

04477

04478

04491

04492

Can be reversed for upstream supply

must be made

(4)

.

For Linergy LGYE and Linergy BS busbars

Free support for busbars connection

2 x

04662

Cover for busbars connection

04926

(4)

Connection to be made according to the busbar drawings supplied by Schneider Electric.

Note:

to make measurements:

b

install a Micrologic control unit capable of displaying the values.

b

or install the CTs on the horizontal busbars; in this case, an additional module is required; add a plain front plate downstream (03801).

Selection of Linergy LGY:

see page B-14,

Linergy LGYE:

see page B-15,

Linergy BS:

see page B-16.

Functional system

Functional units