D-88

Additional information

Practical information

Our circuit breakers have trip units with a

built-in ammeter

(see Micrologic catalogue).

Their use eliminates the need for installing a CT on the busbars.

The CT casing

is a solution for installation of CTs up to 1600 A.

CTs can be installed in the casing (cat. no. 03506).

It is equipped with a frame made up of 2 uprights, adjustable in depth and 2 slotted

cross-members to fix the cables, install CTs or install a busbar support with 75 mm

spacing.

It is secured in the switchgear compartment of a 400 or 600 mm deep cubicle.

The 300 mm duct

allows easier mounting of CTs.

To install 2 CTs, downstream from a circuit-breaker for example, it is often easier

to use a 300 mm wide duct (cat. no. 08403 for 400 mm depth or cat. no. 08603 for

600 mm depth).

DD383909.eps

PD391282.eps

Sealable CT casing with current transformers on bolted

connections.

CT on circuit-breaker downstream connection busbars.

Installation of the current

transformer