Horizontal busbars can be connected to vertical busbars (Linergy LGY or Linergy BS)

in two ways:

bb

in a duct (by a direct connection ordered from the catalogue)

bb

in the rear (with part of the connection to be fabricated by the installer).

DD383948.eps

DD383906.eps

5 mm thick horizontal busbars can be connected to vertical busbars using

connection plate 04634 (y 1000 A) or 04635 (> 1000 A) after drilling holes in the

horizontal bars.

10 mm thick horizontal busbars can be connected to vertical busbars in

2 ways:

bb

using connection plate 04636 (

y

1600 A) or 04637 (> 1600 A) without drilling holes

in the horizontal bars

bb

or with a screw and socket assembly (04645) designed for assembly on a busbar

that has already been mounted.

This bolted solution requires:

bb

holes drilled in the bars (Ø16 mm) for diagonal mounting of the sockets and

screws

bb

conformity with the following mounting rules:

vv

respect the overlap length (2.5 to 5 times the bar thickness)

vv

tighten to a torque of 50 Nm

vv

fit the recommended number of screws, depending on the bar width as explained

below.

Screw + socket

(cat. no. 04645).

Connection plate

(cat. no. 04635).

DD383907.eps

100

80

50/60/80/100

50/60

_

_ _

50/60

100

x2

x4

80

50

60

80

x3

100

_

_ _

x2

x2

x3

50

60

80

100

80

50

60

_ _ _

x4

100

Ø16

10

DD385567.eps

In practice, the real contact area is limited to regions in which the pressure is applied

effectively.

In a bolted overlap assembly, these areas are made up of the areas adjacent to the

bolts, and more precisely under the washers.

Salt spray tests have demonstrated these contact areas.

The number of screws thus determines the effective cross-sectional area through

which the current flows, which corresponds to the area under the washer (minus the

screw hole).

This cross-section area must be close to that of the bar.

Controlled temperature rise

Whatever the connection solution used, the quality and reliability of the contact is

guaranteed, in particular with respect to temperature rise, as long as assembly is

carried out according to our recommendations.