Additional information

Electrical characteristics

Designingconnections

y

630A

Incoming connectionblock andpower

supply block onLinergyBWbusbars

Compact NSX100 to NSX630

Horizontal mounting

Determining the permissible current of NSX100 to NSX630 connection and power

supply blocks as a function of the ambient temperature around the switchboard and

their IP degree of protection.

Device

Rated current of a circuit I

nc

(A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NSX100

TMD-TMG

Incoming connection

block

via the top

04066

100 95 100 92 100 90 97 87 95 85 92

b

b

via the bottom

04067

Power supply block

04060

NSX100STR Incoming connection

block

via the top

04066

100 100 100 97 100 95 100 92 100 90 97

b

b

via the bottom

04067

Power supply block

04060

NSX160

TMD-TMG

Incoming connection

block

via the top

04066

160 152 160 147 160 144 156 140 152 136 147 b

b

via the bottom

04067

Power supply block

04060

NSX160STR Incoming connection

block

via the top

04066

160 160 160 156 160 152 160 147 160 144 156 b

b

via the bottom

04067

Power supply block

04060

NSX250

TMD-TMG

Incoming connection

block

via the top

04066

238 213 231 207 225 200 219 193 213 185 207 b

b

via the bottom

04067

Power supply block

04060

NSX250STR Incoming connection

block

via the top

04066

250 219 245 213 238 207 225 200 219 193 213 b

b

via the bottom

04067

Power supply block

04060

NSX400B/F/

N/H/S/L fixed

Incoming connection

block

04076

400 360 390 350 380 340 370 330 360 320 350 b

b

Power supply block

04070

NSX630B/F/

N/H/S/L fixed

Incoming connection

block

04076

570 520 555 505 540 490 525 470 510 450 495 b

b

Power supply block

04071

The indicated performance characteristics are valid for:

b

b

Compact NSX100/160/250/400 circuit breakers used as incoming or

outgoing devices

b

b

Compact NSX630 circuit breakers used as incoming device.

b

connection not possible.

Note:

the values indicated above have been validated for Prisma switchboards.