181

Additional information

Electrical characteristics

Designingconnections

y

630A

Compact circuit breakersNSX100 to630

Cables

Schneider Electric provides cabling recommendations according to the rating

of the circuit breaker.

The size of cables must be selected according to:

b

b

the level of current

b

b

the ambient temperature around the conductors

b

b

the degree of protection for the switchboard.

When mounting Schneider Electric prefabricated connections, short terminal shields

can be used or not if the function is already integrated in prefabricated connections.

Note:

For some devices, it is recommended to use Schneider Electric prefabricated connections.

If not, switchgears must be equipped with long terminal shields for personnel safety.

Compact NSX100 to NSX250

Copper cable, withstand temperature = 105 °C

Devices

Rated current of a circuit I

nc

(A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

55

NSX100

TMD-TMG

Size

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

I

nc

(A)

100

97.5

95

92.5

90

85

NSX125

TMD-TMG

Size

70 mm²

70 mm²

70 mm²

70 mm²

70 mm²

70 mm²

I

nc

(A)

125

122

119

116

113

100

NSX160

(1)

TMD-TMG

Size

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

I

nc

(A)

160

156

152

147

144

140

NSX250

(1)

TMD-TMG

Size

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

I

nc

(A)

250

244

238

231

225

198

NSX100

STR

Size

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

50 mm²

I

nc

(A)

100

100

100

100

100

100

NSX160

STR

Size

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

95 mm²

I

nc

(A)

160

160

160

160

160

160

NSX250

(2)

STR

Size

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

120 mm²

I

nc

(A)

250

250

237.5

237.5

225

225

(1)

For a withdrawable NSX160 or NSX250 equipped with a Vigi or an insulation-monitoring

module, multiply the In values by 0.9.

(2)

For a withdrawable NSX250 equipped with a Vigi or an insulation-monitoring module, multiply

the In values by 0.86.

Compact NSX400 to NSX630

In case of cable connection

Cable connection is not recommended if the cable sizes are too large. Choose

insulated flexible bar (see table opposite and list of insulated flexible bars).