Table of Contents Table of Contents
Previous Page  180 / 210 Next Page
Information
Show Menu
Previous Page 180 / 210 Next Page
Page Background

180

Additional information

Electrical characteristics

Designingconnections

y

630A

Compact circuit breakersNSX100 to630

Compact NSX100 to NSX250

Insulated flexible copper bars

Devices

Rated current of a circuit I

nc

(A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

55

NSX100

TMD-TMG

Size per phase

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

I

nc

(A)

100

97.5

95

92.5

90

85

NSX125

TMD-TMG

Size per phase

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

I

nc

(A)

125

122

119

116

113

100

NSX160

(1)

TMD-TMG

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I

nc

(A)

160

156

152

147

144

140

NSX250

(1)

TMD-TMG

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I

nc

(A)

250

244

238

231

225

198

NSX100

STR

Size per phase

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

20 x 2

I

nc

(A)

100

100

100

100

100

100

NSX160

STR

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I

nc

(A)

160

160

160

160

160

160

NSX250

(2)

STR

Size per phase

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

20 x 3

I

nc

(A)

250

250

237.5

237.5

225

225

(1)

For a withdrawable NSX160 or NSX250 equipped with a Vigi or an insulation-monitoring

module, multiply the In values by 0.9.

(2)

For a withdrawable NSX250 equipped with a Vigi or an insulation-monitoring module, multiply

the In values by 0.86.

Compact NSX400 to NSX630

Insulated flexible copper bars

Devices

Rated current of a circuit I

nc

(A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

55

NSX400B/F/N/H/S/L

fixed

Size per phase

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

I

nc

(A)

400

400

400

390

380

370

NSX400B/F/N/H/S/L

with Vigi

Size per phase

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

I

nc

(A)

400

390

380

370

360

350

NSX400B/F/N/H/S/L

withdrawable

Size per phase

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

32 x 5

I

nc

(A)

400

390

380

370

360

350

NSX630B/F/N/H/S/L

fixed

Size per phase

32 x 6

32 x 6

32 x 6

32 x 6

32 x 6

32 x 6

I

nc

(A)

630

615

600

585

570

550

NSX630B/F/N/H/S/L

with Vigi or

withdrawable

Size per phase

32 x 8

32 x 8

32 x 8

32 x 8

32 x 8

32 x 8

I

nc

(A)

570

550

535

520

505

490

Note: