B-4

Installation in switchboards

Safety clearances

and minimum distances

General rules

When installing a circuit breaker, minimum distances (safety clearances) must be

maintained between the device and panels, bars and other protection devices

installed nearby. These distances, which depend on the ultimate breaking capacity,

are defined by tests carried out in accordance with standard IEC 60947-2.

If installation conformity is not checked by type tests, it is also necessary to:

use insulated bars for circuit-breaker connections

b

block off the busbars using insulating screens.

b

Installation

recommendations

Compact NS630b to 3200 (fixed devices)

Insulated parts

Metal parts

Live parts

NS630b to 1600

A

0

120

180

B

0

10

60

NS1600b to 3200

A

50

170

230

B

0

10

60

Compact NS630b to 1600 (withdrawable devices)

Insulated parts

Metal parts

Live parts

A

0

0

30

B

10

10

60

C

0

0

30

F

Datum

DB128166

F

146.5

A

(*)

DB128167

A

(*)

B

B

(*)

An overhead clearance of 50 mm is required to

remove the arc chutes.

DB128168

F

40

180

A

DB128169

B

B

C

C