B-2

Altitude derating

Altitude does not significantly affect circuit-breaker characteristics up to 2000 m.

Above this altitude, it is necessary to take into account the decrease in the dielectric

strength and cooling capacity of air.

The following table gives the corrections to be applied for altitudes above 2000

metres. The breaking capacities remain unchanged.

Compact NS630b to 3200

Altitude (m)

2000 3000 4000

5000

Impulse withstand voltage Uimp (kV)

8

7.1

6.4

5.6

Rated insulation voltage (Ui)

800

710

635

560

Maximum rated operationnal voltage 50/60 Hz Ue (V) 690

690

635

560

Rated current 40 °C

1 x In 0.99 x In 0.96 x In 0.94 x In

Intermediate values may be obtained by interpolation.

Vibrations

Compact NS devices resist electromagnetic or mechanical vibrations.

Tests are carried out in compliance with standard IEC 60068-2-6 for the levels

required by merchant-marine inspection organisations (Veritas, Lloyd’s, etc.):

2

b V

13.2 Hz: amplitude ±1 mm

13.2

b V

100 Hz: constant acceleration 0.7 g.

Excessive vibration may cause tripping, breaks in connections or damage to

mechanical parts.

Electromagnetic disturbances

Compact NS devices are protected against:

overvoltages caused by devices that generate electromagnetic disturbances

b

overvoltages caused by an atmospheric disturbances or by a distribution-system

b

outage (e.g. failure of a lighting system)

devices emitting radio waves (radios, walkie-talkies, radar, etc.)

b

electrostatic discharges produced by users.

b

Compact NS devices have successfully passed the electromagnetic-compatibility

tests (EMC) defined by the following international standards:

IEC 60947-2, appendix F

b

IEC 60947-2, appendix B (trip units with Vigi earth-leakage function).

b

The above tests guarantee that:

no nuisance tripping occurs

b

tripping times are respected.

b

Operating conditions

Installation

recommendations

DB128162

2000

(m)

DB128163

DB128164

Compact circuit breakers have been tested for

operation in industrial atmospheres.

It is recommended that the equipment be cooled or

heated to the proper operating temperature and kept

free of excessive vibration and dust.