Compact NS630b to NS1600

(1)

The table below indicates the maximum rated-current value for each type of connection, depending on the ambient temperature.

For mixed connections, use the same derating values as for horizontal connections.

Version

Fixed device

Connection Front or horizontal rear

Vertical rear

temp. Ti

(2)

40 45 50 55 60 65 70 40 45 50 55 60 65 70

NS630b N/L

630 630 630 630 630 630 630 630 630 630 630 630 630 630

NS800 N/L

800 800 800 800 800 800 800 800 800 800 800 800 800 800

NS1000 N/L

1000 1000 1000 1000 1000

1000 1000 1000 1000 1000 1000 1000 1000 1000

NS1250 N

1250 1250 1250 1250 1250 1240 1090 1250 1250 1250 1250 1250 1250 1180

NS1600 N

1600 1600 1560 1510 1470 1420 1360 1600 1600 1600 1600 1600 1510 1460

Version

Withdrawable device

Connection Front or horizontal rear

Vertical rear

temp. Ti

(2)

40 45 50 55 60 65 70 40 45 50 55 60 65 70

NS630b N/L

630 630 630 630 630 630 630 630 630 630 630 630 630 630

NS800 N/L

800 800 800 800 800 800 800 800 800 800 800 800 800 800

NS1000 N/L

1000 1000 1000 1000 1000 1000 920 1000 1000 1000 1000 1000 1000 990

NS1250 N

1250 1250 1250 1250 1250 1170 1000 1250 1250 1250 1250 1250 1250 1090

NS1600 N

1600 1600 1520 1480 1430 1330 1160 1600 1600 1600 1560 1510 1420 1250

Compact NS1600b to 3200

Version

Fixed device

Connection Front or horizontal rear

Vertical rear

temp. Ti

(2)

40 45 50 55 60 65 70 40 45 50 55 60 65 70

NS1600b N

1600 1600 1600 1600 1500 1450 1400 1600 1600 1600 1600 1600 1550 1500

NS2000 N

2000 2000 2000 2000 1900 1800 1700 2000 2000 2000 2000 2000 1900 1800

NS2500 N

2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500

NS3200 N

-

-

-

-

-

-

-

3200 3200 3200 3180 3080 2970 2860

(1)

For a circuit breaker mounted in horizontal position, the derating to be applied is equivalent to that of a front or horizontal rear connected circuit breaker.

(2)

Ti: temperature around the circuit breaker and its connections.

Temperature derating

Compact NS devices equipped

with electronic trip units

Installation

recommendations

Compact circuit breakers have been tested for

operation in industrial atmospheres.

It is recommended that the equipment be cooled or

heated to the proper operating temperature and kept

free of excessive vibration and dust.