B-7

Control wiring

Wiring of voltage releases

During pick-up, the power consumed is approximately 150 to 200 VA.

For low control voltages (12, 24, 48 V), maximum cable lengths are imposed

by the voltage and the cross-sectional area of cables.

Recommended maximum cable lengths (meter).

12 V

24 V

48 V

2.5 mm

2

1.5 mm

2

2.5 mm

2

1.5 mm

2

2.5 mm

2

1.5 mm

2

MN

U source 100 % –

58

35

280

165

U source 85 % –

16

10

75

45

MX-XF

U source 100 % 21

12

115

70

550

330

U source 85 % 10

6

75

44

350

210

Note

:

the indicated length is that of each of the two wires.

24 V DC power-supply module

External 24 V DC power-supply module for Micrologic (F1-, F2+)

do not connect the positive terminal (F2+) to earth

b

the negative terminal (F1-) can be connected to earth, except in IT systems

b

a number of Micrologic control units and M6C modules can be connected to the

b

same 24 V DC power supply (the consumption of a Micrologic control unit

or an M6C module is approximately 100 mA)

do not connect any devices other than a Micrologic control unit or an M6C

b

module if voltage > 480 V AC or in an environment with high level of electromagnetic

desturbance

the maximum length for each conductor is ten metres. For greater distances,

b

it is advised to twist the supply wires together

the 24 V DC supply wires must cross the power cables perpendicularly.

b

If this is difficult, it is advised to twist the supply wires together

the technical characteristics of the external 24 V DC power-supply module

b

for Micrologic control units are indicated on

page A-28

.

Communication bus

do not connect the positive terminal (E1) to earth

b

the negative terminal (E2) can be connected to earth

b

a number of "device" or "chassis" communication modules can be connected

b

to the same 24 V DC power supply (the consumption of each module is

approximately 30 mA).

Note:

wiring of ZSI: it is recommended to use twisted shielded cable. The shield must be

connected to earth at both ends.

Installation

recommendations