A-72

Electrical and mechanical

accessories

Compact NS1600b to 3200

(cont.)

Compact NS1600b to 3200 circuit breakers may be

equipped with an MX shunt release, an MN

undervoltage release or a delayed undervoltage

release (MNR = MN + delay unit).

Remote tripping

This function opens the circuit breaker via an electrical order. It is made up of:

a shunt release 2

b

nd

MX

or an undervoltage release MN

b

or a delayed undervoltage release MNR = MN + delay unit.

b

These releases (2

nd

MX or MN) cannot be operated by the communication bus.

The delay unit, installed outside the circuit breaker, may be disabled by an

emergency OFF button to obtain instantaneous opening of the circuit breaker.

Wiring diagram for the remote-tripping function

Voltage releases 2

nd

MX

When energised, the 2

nd

MX voltage release instantaneously opens the circuit

breaker. A continuous supply of power to the 2

nd

MX locks the circuit breaker in the

OFF position.

Functions and characteristics

Characteristics

Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480

V DC

12 - 24/30 - 48/60 - 100/130 - 200/250

Operating threshold

0.7 to 1.1 Un

Permanent locking function

0.85 to 1.1 Un

Consumption (VA or W)

pick-up: 200 (80 ms)

hold: 4.5

Circuit breaker response

50 ms±10

time at Un

Instantaneous voltage releases MN

The MN release instantaneously opens the circuit breaker when its supply voltage

drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on

the release, it is impossible to close the circuit breaker, either manually or electrically.

Any attempt to close the circuit breaker has no effect on the main contacts. Circuit

breaker closing is enabled again when the supply voltage of the release returns to 85

% of its rated value.

Characteristics

Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480

V DC

24/30 - 48/60 - 100/130 - 200/250

Operating

opening

0.35 to 0.7 Un

threshold

closing

0.85 Un

Consumption (VA or W)

pick-up: 200 (200 ms)

hold: 4.5

MN consumption

pick-up: 400 (200 ms)

hold: 4.5

with delay unit (VA or W)

Circuit breaker response

90 ms±5

time at Un

MN delay units

To eliminate circuit breaker nuisance tripping during short voltage dips, operation of

the MN release can be delayed. This function is achieved by adding an external

delay unit in the MN voltage-release circuit. Two versions are available, adjustable

and non-adjustable.

Characteristics

Power supply

non-adjustable

100/130 - 200/250

V AC 50-60 Hz /DC

adjustable

48/60 - 100/130 - 200/250 - 380/480

Operating threshold

opening

0.35 to 0.7 Un

closing

0.85 Un

Consumption of delay

pick-up: 200 (200 ms)

hold: 4.5

unit alone (VA or W)

Circuit breaker response

non-adjustable

0.25 s

time at Un

adjustable

0.5 s - 0.9 s - 1.5 s - 3 s

DB128138

Opening

order

D2

D1

MN

DB128137

C2

C1

MX

Opening

order

DB128139

MN

D2

D1

10 12

3 6

Delayed

opening

order

Instantaneous

opening

order

Delay

unit

056421

MX voltage release