A-67

Chassis locking

DB128071

1

2

8

10

9

7

5

6

4

3

mismatch protection

1

door interlock

2

racking interlock

3

keylock locking

4

padlock locking

5

position indicator

6

chassis front plate

7

(accessible with cubicle

door closed)

crank entry

8

reset button

9

crank storage

10

PB104366A32

PB104367A34

“Disconnected” position locking by padlocks (standard) or

keylocks (VSPD option)

Mounted on the chassis and accessible with the door closed, these devices lock the

circuit breaker in the disconnected position in two manners:

using padlocks (standard), up to three padlocks (not supplied)

b

using keylocks (optional), one or two different keylocks are available.

b

Profalux and Ronis keylocks are available in different options:

one keylock

b

one keylock mounted on the device + one identical keylock supplied separately,

b

using the same key, for interlocking with another device

one (or two) keylocks mounted on the device + one (or two) identical keylocks

b

supplied separately, for interlocking with another device.

A locking kit (without locks) is available for installation of one or two keylocks (Ronis,

Profalux, Kirk or Castell).

“Connected”, “disconnected” and “test” position locking

The connected, disconnected and test positions are shown by an indicator and are

mechanically indexed.

The racking crank blocks when the exact position is obtained.

A release button is used to free it.

As standard, the circuit breaker can be locked only in "disconnected position". On

request, the locking system may be modified to lock the circuit breaker in any of the

three positions: "connected", "disconnected" or "test".

Door interlock catch VPEC

Mounted on the right or left-hand side of the chassis, this device inhibits opening of

the cubicle door when the circuit breaker is in connected or test position. It the

breaker is put in the connected position with the door open, the door may be closed

without having to disconnect the circuit breaker.

Racking interlock VPOC

This device prevents insertion of the crank when the cubicle door is open (device

cannot be connected).

Mismatch protection VDC

Mismatch protection ensures that a circuit breaker is installed only in a chassis with

compatible characteristics. It is made up of two parts (one on the chassis and one on

the circuit breaker) offering twenty different combinations that the user may select.

”Disconnected” position

locking by padlocks.

”Disconnected” position

locking by keylocks.

PB104352A32

Door interlock.

PB104368 A32

Racking interlock.

PB100815-32R_SE

Mismatch protection.