A-64

Electrical and mechanical

accessories

Compact NS630b to 1600

(cont.)

Manually operated circuit breakers may be equipped

with an MX shunt release, an MN undervoltage release

or a delayed undervoltage release (MN + delay unit).

Electrically operated circuit breakers are equipped as

standard with a remote-operating mechanism to

remotely open or close the circuit breaker. An MX shunt

release or an MN undervoltage release (instantaneous

or delayed) may be added.

MX voltage release.

Remote tripping

This function opens the circuit breaker via an electrical order. It is made up of:

a shunt release (2

b

nd

MX)

or an undervoltage release MN

b

or a delayed undervoltage release MN + delay unit.

b

These releases (2nd MX or MN) cannot be operated by the communication bus.

The delay unit, installed outside the circuit breaker, may be disabled by an

emergency OFF button to obtain instantaneous opening of the circuit breaker.

Wiring diagram for the remote-tripping function

Voltage releases 2

nd

MX

When energised, the 2

nd

MX voltage release instantaneously opens the circuit

breaker. A continuous supply of power to the 2

nd

MX locks the circuit breaker in the

OFF position.

Characteristics

Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480

V DC

12 - 24/30 - 48/60 - 100/130 - 200/250

Operating threshold

0.7 to 1.1 Un

Permanent locking function

0.85 to 1.1 Un

Consumption (VA or W)

pick-up: 200 (200 ms)

hold: 4.5

Circuit breaker response

50 ms ±10

time at Un

Instantaneous voltage releases MN

The MN release instantaneously opens the circuit breaker when its supply voltage

drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on

the release, it is impossible to close the circuit breaker, either manually or electrically.

Any attempt to close the circuit breaker has no effect on the main contacts. Circuit

breaker closing is enabled again when the supply voltage of the release returns to

85 % of its rated value.

Characteristics

Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480

V DC

24/30 - 48/60 - 100/130 - 200/250

Operating

opening

0.35 to 0.7 Un

threshold

closing

0.85 Un

Consumption (VA or W)

pick-up: 200 (200 ms)

hold: 4.5

MN consumption

pick-up: 400 (200 ms)

hold: 4.5

with delay unit (VA or W)

Circuit breaker response

90 ms ±5

time at Un

MN delay units

To eliminate circuit breaker nuisance tripping during short voltage dips, operation of

the MN release can be delayed. This function is achieved by adding an external

delay unit in the MN voltage-release circuit. Two versions are available, adjustable

and non-adjustable.

Characteristics

Power supply

non-adjustable

100/130 - 200/250

V AC 50-60 Hz /DC

adjustable

48/60 - 100/130 - 200/250 - 380/480

Operating threshold

opening

0.35 to 0.7 Un

closing

0.85 Un

Consumption of delay

pick-up: 200 (200 ms)

hold: 4.5

unit alone (VA or W)

Circuit breaker response

non-adjustable

0.25 s

time at Un

adjustable

0.5 s - 0.9 s - 1.5 s - 3 s

Functions and characteristics

DB128137

C2

C1

MX

Opening

order

DB128138

Opening

order

D2

D1

MN

DB128139

MN

D2

D1

10 12

3 6

Delayed

opening

order

Instantaneous

opening

order

Delay

unit

056421