A-60
Electrical and mechanical
accessories
Compact NS630b to 1600
(cont.)
Insulation of live parts
Connection shield
Mounted on fixed, front-connection devices, this shield
insulates power-connection points, particularly when
cables with lugs are used
Interphase barriers
These barriers are flexible insulated partitions used to
reinforce isolation of connection points in installations
with busbars, whether insulated or not.
Barriers are installed vertically between front or rear
connection terminals.
They are mandatory for voltages
u
500 V for both fixed
and withdrawable products and for L and LB types,
whatever the voltage.
Safety shutters (standard)
Mounted on the chassis, the safety shutters
automatically block access to the disconnecting
contact cluster when the device is in the disconnected
or test positions (degree of protection IP20). When the
device is removed from its chassis, no live parts are
accessible.
The shutters can be padlocked (padlock not supplied)
to:
prevent connection of the device
b
lock the shutters in the closed position.
b
Functions and characteristics
E45190
Compact NS equipped with connection shield.
DB128127
Connection shield.
DB128128
Interphase barriers for fixed
device, front connection.
DB128129
Interphase barriers for fixed
device, rear connection.
DB128130
Interphase barriers for
withdrawable device, rear
connection.
DB128131
Safety shutters.