Background Image
Table of Contents Table of Contents
Previous Page  76 / 148 Next Page
Information
Show Menu
Previous Page 76 / 148 Next Page
Page Background

A-60

Electrical and mechanical

accessories

Compact NS630b to 1600

(cont.)

Insulation of live parts

Connection shield

Mounted on fixed, front-connection devices, this shield

insulates power-connection points, particularly when

cables with lugs are used

Interphase barriers

These barriers are flexible insulated partitions used to

reinforce isolation of connection points in installations

with busbars, whether insulated or not.

Barriers are installed vertically between front or rear

connection terminals.

They are mandatory for voltages

u

500 V for both fixed

and withdrawable products and for L and LB types,

whatever the voltage.

Safety shutters (standard)

Mounted on the chassis, the safety shutters

automatically block access to the disconnecting

contact cluster when the device is in the disconnected

or test positions (degree of protection IP20). When the

device is removed from its chassis, no live parts are

accessible.

The shutters can be padlocked (padlock not supplied)

to:

prevent connection of the device

b

lock the shutters in the closed position.

b

Functions and characteristics

E45190

Compact NS equipped with connection shield.

DB128127

Connection shield.

DB128128

Interphase barriers for fixed

device, front connection.

DB128129

Interphase barriers for fixed

device, rear connection.

DB128130

Interphase barriers for

withdrawable device, rear

connection.

DB128131

Safety shutters.