A-63

Rotary handles

There are two types of rotary handle:

direct rotary handle

b

extended rotary handle.

b

There are two models:

standard with a black handle

b

VDE with a red handle and yellow front for machine-tool control.

b

Direct rotary handle

Degree of protection IP40, IK07.

The direct rotary handle maintains:

visibility of and access to trip unit settings

b

suitability for isolation

b

indication of the three positions O (OFF), I (ON) and tripped

b

access to the "push to trip" button

b

circuit breaker locking capability in the OFF position by one to three padlocks,

b

shackle diameter 5 to 8 mm (not supplied).

It replaces the circuit breaker front cover.

Accessories transform the standard direct rotary handle for the following situations:

a higher degree of protection (IP43, IK07)

b

machine-tool control, complying with CNOMO E03.81.501, IP54, IK07.

b

Extended rotary handle

Degree of protection IP55, IK07.

This handle makes it possible to operate circuit breakers installed at the back of

switchboards, from the switchboard front.

It maintains:

suitability for isolation

b

indication of the three positions O (OFF), I (ON) and tripped

b

access to trip unit settings, when the switchboard door is open

b

circuit breaker locking capability in the OFF position by one to three padlocks,

b

shackle diameter 5 to 8 mm (not supplied).

The door cannot be opened if the circuit breaker is ON or locked.

The extended rotary handle is made up of:

a unit that replaces the front cover of the circuit breaker (secured by screws)

b

an assembly (handle and front plate) on the door that is always secured in the

b

same position, whether the circuit breaker is installed vertically or horizontally

an extension shaft that must be adjusted to the distance. The min/max distance

b

between the back of circuit breaker and door is 218/605 mm.

M6C programmable contacts

These contacts, used with the Micrologic P control units, may be programmed via the

control unit keypad or via a supervisory station with the COM communication option.

They require an external power supply module.

They indicate:

the type of fault

b

instantaneous or delayed threshold overruns.

b

They may be programmed:

with instantaneous return to the initial state

b

without return to the initial state

b

with return to the initial state following a delay.

b

Characteristics

M6C

Minimum load

100 mA/24 V

Breaking capacity (A)

V AC

240

5

p.f.: 0.7

380

3

V DC

24

1.8

48

1.5

125

0.4

250

0.15

M6C: external 24 V DC power supply required (consumption 100 mA).

PB100781-32_SE

M6C programmable contacts:

circuit breaker external relay with six independent changeover

contacts controlled from the circuit breaker via a three-wire

connection (maximum length is 10 meters).

PB104828

Compact NS with a direct rotary handle.

PB104829

Compact NS with an extended rotary handle.

DB101170

1 3

22 24 16 18 10 12 4 6 9

5

20

14

8

2

11