A-55

Connections accessories

To ensure performance and isolation, depending on

the type of circuit breaker (N, L, LB) and type of

connection, certain isolation accessories are

mandatory.

Type of accessories

For Compact NS630b to NS1600

Fixed:

Withdrawable:

Front connection Rear connection Front connection Rear connection

Vertical-connection adapters

N, L

-

N, L, LB

-

Set of bare-cable connectors

and terminal shields for

ratings

y

1250 A

N

-

-

-

Cable lug adapters

N, L

N, L, LB

N, L, LB

N, L, LB

Interphase barriers

N, L, LB

N, L, LB

-

N, L, LB

(1) (2)

(1)

(1)

Spreaders

N, L

N, L, LB

N, L, LB

N, L, LB

Connection shield

N, L

-

-

-

Safety shutters with locking

by padlocks (IP20)

-

-

N, L, LB

(standard)

N, L, LB

(standard)

Arc chute screen

N, L

-

-

-

(1) (2)

(1)

Mandatory for voltages

u

500 V unless using the bare-cable connector + terminal shield kit.

(2)

Mandatory for fixed devices with L and LB performance levels, whatever the voltage.

DB128085

DB128092

DB128091

DB128090

DB128089

DB128088

DB128087

DB128086