Background Image
Table of Contents Table of Contents
Previous Page  172 / 408 Next Page
Information
Show Menu
Previous Page 172 / 408 Next Page
Page Background

7/40

Technical

Section 11

Dimensions

Section 12

7

iTR transformers (cont.)

Measurement

indication

Connection

DB123272

Tightening

torque

Copper cables

Rigid

Flexible or with

ferrule

0.5 N.m < 2.5 mm

2

< 2.5 mm

2

PZ1

6 mm

6 mm

Technical data

Main characteristics

Primary voltage

230 V AC ±10 %

Secondary voltage

on load

For bell transformers 8-12-24 V AC ±15 %

For safety transformers 12-24 V AC ±5 %

Transformer

catalogue numbers

Rated

secondary voltage

Off load voltage

A9A15214

8 V

12 V

A9A15213

8 V

12 V

12 V

16 V

A9A15216

8 V

13 V

12 V

18 V

A9A15212

8 V

13 V

12 V

18 V

A9A15215

12 V

16 V

24 V

32 V

A9A15218

12 V

14 V

24 V

28 V

A9A15219

12 V

14 V

24 V

28 V

A9A15220

12 V

14 V

24 V

28 V

A9A15222

12 V

14 V

24 V

28 V

Additional characteristics

Degree of protection

(IEC 60529)

Device only

IP20 with terminal shield

Operating temperature

-20°C to +55°C

Storage temperature

-25°C to +80°C

Note: Transformers have an off load operating voltage that is higher than the rated voltage.

For loads that are sensitive to overloads (electro-magnetic circuits), the transformer must be

made to operate at ln. After operation of the protection device upon an overload, cut-off the

power supply and let the transformer cool down before restart.

IP20

Clip on DIN rail 35 mm.

Bell transformer: indifferent position of installation.

Safety transformer: vertical position.

Weight (g)

iTR

Type

Cat. no.

Weight

Bell

A9A15212

384

A9A15213

240

A9A15214

237

A9A15215

633

A9A15216

275

Safety

A9A15218

1082

A9A15219

1125

A9A15220

1190

A9A15222

1309

Dimensions (mm)

DB123215

89

45

36

54

90

5

16

39

A9A15212

A9A15213

A9A15214

A9A15216

A9A15215

A9A15218

A9A15219

A9A15220

A9A15222

DB123957

DB123310

DB123312

DB122945

DB122946