STI isolatable fuse carriers (cont.)

Control and

circuit protection

Dimensions (mm)

DB122933

54

81 35

45

5.5

16

36

18

3P / 3P+N

2P

1P / 1P+N

44

STI

DB122934

A

B

C

aM, gG

aM, gG fuse cartridge

Type

A B C

8.5 x 31.5 mm 8.5

31.5 10.3

10.3 x 38 mm 10.3 38

10.5

Technical data

Main characteristics

Insulation voltage (Ui)

500 V

Breaking capacity according to IEC 60269-2

y

400 V 50 kA

Pollution degree

3

Operating frequency (Hz)

50/60

Additional characteristics

Degree of protection Device in modular enclosure IP40

Insulation classe II

Operating temperature

-20°C to +60°C

Storage temperature

-40°C to +80°C

Maximum dissipated power per pole of STI isolatable fuse-carriers

Fuse cartridge type

Ith

Pmax

8.5 x 31 mm

aM

10 A

2.5 W

gG

20 A

2.5 W

10.3 x 38 mm

aM

16 A

3 W

gG

25 A

3 W

Maximum dissipated power per fuse cartridges

Fuse cartridge type

Ith

Pmax

8.5 x 31 mm

aM

2 to 10 A

0.9 W

gG

2 to 10 A

2.5 W

10.3 x 38 mm

aM

2 to 25 A

1.2 W

gG

2 to 25 A

3 W

Clip on DIN rail 35 mm.

IP40

DB123309