Page Background

7/46

Technical

Section 11

Dimensions

Section 12

7

SBI fuse holder

with indicator light

Local control

selector switches

b

b

SBI fuse holders provide overload and short-circuit protection.

b

b

They are used for industrial applications requiring a high breaking capacity.

b

b

They perform the isolation function and must not be used as switches.

b

b

They are equipped with an indicator light indicating blowing of the fuse cartridge:

to be equipped with aM or gG (gL-gl) type fuse cartridge without striker.

The general purpose fuse (gG fuse) provides overload and short-circuit protection.

The fuse for motor application (

aM fuse

) only provides short-circuit protection.

It is used for protection of loads with a high peak current (motors, transformer

primaries, etc.).

Catalogue numbers

Fuse cartridge

SBI fuse holder

Type

Network type

Rating Voltage

rating (Ue)

Short-circuit

current (Isc)

aM gG aM gG

N

1P

1P+N

(1)

2P

3P

3P+N

(1)

N

1

2

N 1

2

3

4

1

2

3

4

1

2

5

6

3

4

1

2

5

6

N

14 x 51

mm

10 A 690 V CA 120 kA 120 kA

DF2EA10 DF2EN10 MGN15708

3 modules

of 9 mm

MGN15707

3 modules

of 9 mm

MGN15709

6 modules

of 9 mm

MGN15710

6 modules

of 9 mm

MGN15711

9 modules

of 9 mm

MGN15712

12 modules

of 9 mm

12 A 690 V CA 120 kA -

DF2EA12 -

16 A 690 V CA 120 kA 120 kA

DF2EA16 DF2EN16

20 A 690 V CA 120 kA 120 kA

DF2EA20 DF2EN20

25 A 690 V CA 120 kA 120 kA

DF2EA25 DF2EN25

32 A 500 V CA 120 kA 120 kA

DF2EA32 DF2EN32

40 A 500 V CA 120 kA 120 kA

DF2EA40 DF2EN40

50 A 400 V CA 120 kA 120 kA

DF2EA50 DF2EN50

22 x 58

mm

32 A 690 V CA 80 kA 80 kA

DF2FA32 DF2FN32 MGN15714

4 modules

of 9 mm

MGN15713

4 modules

of 9 mm

MGN15715

8 modules

of 9 mm

MGN15716

8 modules

of 9 mm

MGN15717

12 modules

of 9 mm

MGN15718

16 modules

of 9 mm

40 A

690 V CA 80 kA 80 kA

DF2FA40 DF2FN40

50 A 690 V CA 80 kA 80 kA

DF2FA50 DF2FN50

63 A 690 V CA 80 kA 80 kA

DF2FA63 DF2FN63

80 A 690 V CA 80 kA 80 kA

DF2FA80 DF2FN80

100 A 400 V CA 120 kA 120 kA

DF2FA100 DF2FN100

125 A 400 V CA 120 kA -

DF2FA125 -

Operating frequency: 50/60 Hz

DB112796

DB112797

DB112798

DB112799

DB112800

IEC EN 60947-3

PB102092_SE

PB102097_SE

MGN15707

MGN15712

PB102100_SE

PB102104_SE

MGN15714

MGN15718

(1) The neutral pole comes equipped with a locked tube.

DB110801

PB102098-20