Background Image
Table of Contents Table of Contents
Previous Page  174 / 408 Next Page
Information
Show Menu
Previous Page 174 / 408 Next Page
Page Background

7/42

Technical

Section 11

Dimensions

Section 12

7

STI isolatable fuse carriers

Control and

circuit protection

Function

STI

The isolatable fuse-carriers provide overload and short-circuit protection and are

used in the tertiary and industrial sectors.

Fuse-links

aM, gG (gl, gL) types for STI.

Indicator light

230 V neon indicator adaptable on STI.

Description

STI

n

Isolation of all poles is guaranteed for the 2P, 3P, and 3P + N versions during

factory assembly

n

Positive contact indication

n

To be equiped with aM or gG (gL - gl) type fuse-links, with or without fuse

blowing indicator

Rating

Size

aM

gG

(A)

(mm)

fuse

fuse

0.5 to 20

8.5 x 31.5

n

1 to 20

10.3 x 38

n

25 to 32

10.3 x 38

n

n

Fuse-carrier: Captive, additional housing is provided for a spare fuse

n

Optional indication by indicator lights (see accessories)

n

Connection by tunnel terminals for rigid cables up to 10 mm

2

and flexible cables

up to 6 mm

2

n

Complies with standard IEC 947.3

Fuse-links

n

aM, gG (gL - gl) types

n

Fuse-link without striker pin

n

Breaking capacity as in the standards

Dimensions

Rating

Operating Breaking capacity

(ø x L)

(A)

voltage

(kA)

(mm)

(V AC)

aM gG

8.5 x 31.5

All

380

20

20

10 x 38

<10

500

80

80

25

660

80

80

n

Complies with standards NF C 60 200 and NF C 63 210

n

Véritas and Lloyds approved

Indicator light (option)

Technical data

230V AC neon (400V AC maximum)

Allows indication of fuse blowing (lift after blowing)

Specific characteristics

STI 1P + N and 3P + N

n

Disconnection of the phase and neutral in the normal dimensions of the phase

(2 modules of 9 mm)

n

Phase opening causes compulsory opening of the neutral

n

The phase opens before the neutral on isolation and closes after the neutral on

circuit closing