7/36

Technical

Section 11

Dimensions

Section 12

7

iSW switches (cont.)

Control

Local control

Technical data

Main characteristics

20, 32 A iSW

Insulation voltage (Ui)

Without indicator light

b

b

1P: 250 V AC

b

b

2P, 3P, 4P: 500 V AC

With indicator light

250 V AC

Pollution degree

2

Power circuit

Rated impulse withstand voltage

(Uimp)

4 kV

Operating category

AC - 22 A

Permissible rated short-time

withstand current (Icw)

-

Conditional rated short-circuit current

(Inc)

3 kA to IEC/EN 60669-2-4

Rated short-circuit closing current

(Icm)

-

Using direct current

48 V (110 V with 2 poles in series)

Additional characteristics

Degree of protection

IP40 on the front panel

Endurance (O-C)

Mechanical

300,000 cycles

Electrical

30,000 cycles

Operating temperature

-20°C to +50°C

Storage temperature

-40°C to +70°C

Tropicalization

Treatment 2 (relative humidity 95% at 55°C)

Catalogue numbers (cont.)

Auxiliary

Type

Width in 9 mm

modules

OF iSW

Rating

Voltage (Ue)

DB122821

11

14 12

3 A

415 V AC

A9A15096

2

6 A

250 V AC

PB105264-40

OF iSW

DB123597

IP40