15 Moulded Case Breakers 0115
ABB Low Voltage
2
20A motor start-up unit
Protection and operation are guaranteed by circuit-
breaker XT2 MA In20A 3p in conjunction with the
thermal relay and contactor.
200A motor start-up unit
Protection and operation are guaranteed by circuit-
breaker XT4 Ekip M-LRIU In200A 3p in conjunction
with the contactor.
ABB |
SACE Tmax Moulded-case circuit-breakers 13
4
4
3
3
3
3
3
Start-up is a particularly critical phase for the motor itself and for the installation powering it.
Even rated service needs to be adequately monitored and protected in order to respond to
any faults that might occur.
When it comes to direct starting, ABB SACE proposes two different solutions:
n
a conventional system with three poles circuit-breaker equipped with a magnetic only trip
unit for protection against short-circuits, a.thermal relay for protection against overloads
and phase failure or imbalance, and a contactor to operate the motor;
n
an advanced protection system which integrates all the protection and monitoring functions,
and a contactor for operating the motor, in the circuit-breaker itself.
Releases
Frame [A]
160
200
400
630
800
1000
1600
MF-MA (Magnetic only trip unit)
Tmax XT2-XT3-XT4
I (Basic Magnetic only trip unit)
Tmax XT2-XT4-T5-T6-T7-T8
LIU (Advanced Magnetic only trip unit)
Tmax XT2-XT4
LRIU (Advanced Magnetic only trip unit)
Tmax XT2 – XT4 – T5 – T6
Circuit-breakers for motor protection
Coordination tables
Suitable devices for protection and motor operation can be identified, given the type of starting, the electrical characteris-
tics of the installation and the characteristics of the motor.
Motor
MCCB
Contactor
Thermal relay
Rated
power
Rated
current
Type
Magnetic protection
setting
Type
Type
Setting
range
I max
Pe
Ie
[A]
min [A]
max [A]
[A]
5.50
11.50 XT2S 160 MF 12.5
175
AF38
EF19-18.9 5.70
18.90 12.50
7.50
15.50
XT2S 160 MA 20
240
AF38
EF19-18.9 5.70
18.90 18.90
9.00
18.60
XT2S 160 MA 20
280
A50
EF45-30
9
30
20
11.00
22.00
XT2S 160 MA 32
320
A50
EF45-30
9
30
30
2
20A motor start-up unit
Protection and operation are guaranteed by circuit-
breaker XT2 MA In20A 3p in conjunction with the
thermal relay and contactor.
200A motor start-up unit
Protection and operation are guaranteed by circuit-
breaker XT4 Ekip M-LRIU In200A 3p in conjunction
with the contactor.
ABB |
SACE Tmax Moulded-case circuit-breakers 13
4
4
3
3
3
3
3
Start-up is a particularly critical phase for the motor itself and for the installation powering it.
Even rated service needs to be adequately monitored and protected in order to respond to
any faults that might occur.
When it comes to direct starting, ABB SACE proposes two different solutions:
n
a conventional system with three poles circuit-breaker equipped with a magnetic only trip
unit for protection against short-circuits, a.thermal relay for protection against overloads
and phase failure or imbalance, and a contactor to operate the motor;
n
an advanced protection system which integrates all the protection and monitoring functions,
and a contactor for operating the motor, in the circuit-breaker itself.
Releases
Frame [A]
160
200
400
630
800
1000
1600
MF-MA (Magnetic only trip unit)
Tmax XT2-XT3-XT4
I (Basic Magnetic only trip unit)
Tmax XT2-XT4-T5-T6-T7-T8
LIU (Advanced Magnetic only trip unit)
Tmax XT2-XT4
LRIU (Advanced Magnetic only trip unit)
Tmax XT2 – XT4 – T5 – T6
Circuit-breakers for motor protection
Coordination tables
Suitable devices for protection and motor operation can be identified, given the type of starting, the electrical characteris-
tics of the installation and the characteristics of the motor.
Motor
MCCB
Contactor
Thermal relay
Rated
power
Rated
current
Type
Magnetic protection
setting
Type
Type
Setting
range
I max
Pe
Ie
[A]
min [A]
max [A]
[A]
5.50
11.50 XT2S 160 MF 12.5
175
AF38
EF19-18.9 5.70
18.90 12.50
7.50
15.50
XT2S 160 MA 20
240
AF38
EF19-18.9 5.70
18.90 18.90
9.00
18.60
XT2S 160 MA 20
280
A50
EF45-30
9
30
20
11.00
22.00
XT2S 160 MA 32
320
A50
EF45-30
9
30
30
2
20A motor start-up unit
Protection and operation are guaranteed by circuit-
breaker XT2 MA I 20A 3p in conjunction with the
thermal relay and contactor.
200A motor start-up unit
Prot ction and operation are guaranteed by circui -
breaker XT4 Ekip M-LRIU In200A 3p in conjunction
with the contactor.
ABB |
SACE Tmax Moulded-case circuit-breakers 13
4
4
3
3
3
3
3
Start-up is a particularly critical phase for the otor itself and for the installation powering it.
Even rated service needs to be adequately monitored and protected in order to respond to
any faults that might occur.
When it comes to direct starting, ABB SACE proposes two different solutions:
n
a c nventional system wit three poles circuit-breaker equipp d with a magnetic nly trip
unit for protection against short-circuits, .thermal relay for protection against overloads
and phase failur or imbalance, and a contactor to operat the motor;
n
an advanced protection system which integrates all the protection and monitoring functions,
and a contactor for operating the motor, in the circuit-breaker itself.
Releases
Frame [A]
160
200
400
630
800
1000
1600
MF-MA (Magnetic only trip unit)
Tmax XT2-XT3-XT4
I (Basic M gn tic only trip u it)
Tmax XT2-XT4-T5-T6-T7-T8
LIU (Advanced Magnetic only trip unit)
Tmax XT2-XT4
LRIU (Advanced Magnetic only trip unit)
Tmax XT2 – XT4 – T5 – T6
Circuit-breakers for motor protection
Coordination tables
Suitable devices for protection and moto operation can be identified, given the type of starting, the electrical characteris-
tics of the installation and the characteristics of the motor.
Motor
MCCB
Contactor
Thermal relay
Rated
power
Rated
current
Type
Magnetic protection
setting
Type
Type
Setting
range
I max
Pe
Ie
[A]
min [A]
max [A]
[A]
5.50
11.50 XT2S 160 MF 12.5
175
AF38
EF19-18.9 5.70
18.90 12.50
7.50
15.50
XT2S 160 MA 20
240
AF38
EF19-18.9 5.70
18.90 18.90
9.00
18.60
XT2S 160 MA 20
280
A50
EF45-30
9
30
20
11.00
22.00
XT2S 160 MA 32
320
A50
EF45-30
9
30
30
Start-up is a particularly critical phase for the motor itself and for the installation powering it. Even rated service needs to be adequately
monitored and protected in order to respond to any faults that might occur. When it comes to direct starting, ABB SACE proposes two
different solutions:
a onventional s stem wi h three poles circuit-breaker equi ped with a magnetic only trip unit for pro ection against short-circuits, a
thermal relay for protection against overloads and phase failure or imbalance, and a contactor to operate the motor;
an advanced p otection system which integrates all the protection and monitoring functions, and a contactor for operating the motor,
in the circuit-breaker itself.
3
- 200A motor start-up unit
Protection and operation are guaranteed by circuitbreaker
XT4 Ekip M-LRIU In200A 3p in conjunction with the contactor.
4
- 20A motor start-up unit
Protection and operation are guaranteed by circuit breaker
XT2 MA In20A 3p in conjunction with the thermal relay and
contactor.
Releases
Frame [A]
160
250
400
500
630
800
1000
1600
MF-MA (Magnetic only trip unit)
Tmax XT2-XT3-XT4
I (Basic Magnetic only trip unit)
Tmax XT2-XT4-T5-T6-T7-T8
LIU (Advanced Magnetic only trip unit)
Tmax XT2-XT4
LRIU (Advanced Magne ic only trip unit)
Tmax XT2-XT4-T5-T6
Motor
MCCB
Contactor
Thermal relay
Rated
power
Rated
current
Type
Magnetic protection
setting
Type
Type
Setting
range
Pe
Ie
[A]
min [A]
max [A]
I max [A]
5.50
11.50
XT2S 160 MF 12.5
175
AF38
EF19-18.9
5.70
18.90
12.50
7.50
15.50
XT2S 160 MF 20
240
AF38
EF19-18.9
5.70
18.90
18.90
9.00
8.60
XT2S 160 MF 20
280
A50
EF45-30
9
30
30
11.
22.00
2S 160 MF 32
320
A50
EF45-30
9
30
30
Circuit-breakers for m tor protection
Coordination tables
Suitable devices for protection and motor operation can be identified, given the type of starting, the electrical characteristics
of the installation and the characteristics of the motor.
4
3
3