ClimaSys

Thermal management system

Thermal balance

Cooling

Air-air exchangers

Air-air exchangers are devices that combine efficiency and simplicity. The hot air

flows of the enclosure and the cold of the surrounding environment, created by two

fans, circulate on either side of hermetic separation walls, preventing the penetration

of dust or moisture in the enclosure. The hot air from the switchboard reheats these

walls, which in turn are cooled by the fresh air from outside. The transfer always

takes place from the hotter side to the cooler side. This is why these devices can

only be used if the ambient temperature is at least 5°C lower than the desired

temperature inside the enclosure.

The aluminium exchange cassette forms the core of the system. This element can

be cleaned easily by simply removing it. In addition, the permanent operation of

the internal fan prevents the appearance of hot spots in the electrical switchboard.

The temperature regulation system integrated in the unit turns the external circuit

fan on and off.

Air-water exchangers

Air-water exchangers operate on the same principle as air-air exchangers.

Fresh air from the outside is replaced with cold water supplied by a network installed

on the industrial site. This change of fluid makes it possible to evacuate much larger

amounts of heat and, possibly, to reduce the temperature in the enclosure below

the temperature of the ambient air.

Temperature control in the enclosure is carried out by modulating the water flow.

The water circuit is protected by a shut-off device: your electrical installation is safe.

Cooling units

Cooling units can be used in the harshest environments, where the temperature

can reach 55°C. These devices are especially recommended when the desired

temperature inside the enclosure must be lower than the ambient temperature

or when a large amount of heat needs to be evacuated. As in the case of the

exchangers, they do not affect the IP of the switchboard.

The filter, placed at the inlet of the external air circuit, allows it to operate even when

the ambient air is charged with dust or oil particles. Easily replaceable and quite

inexpensive, this device guarantees the efficiency of the device throughout its

service life. These devices control the temperature inside the enclosure and include

an alarm function for signalling operational anomalies.

DB300453-13

The ambient temperature is higher than the desired temperature inside

the enclosure.

DB300453-13

The ambient temperature is lower than the desired temperature inside

the enclosure.

The ProClima calculation software, available on our website, is an indispensable tool

for the selection of a thermal auxiliary.