![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0514.jpg)
514
PB501160-24
PB501158-24
PB501172-25
PB501162-25
ClimaSysCC
Thermal management system
Characteristics, selectionguide
Mechanical thermostats
Characteristics Thermostat
Thermostat
Thermostat
Double Thermostat
With NC contact
With NO contact
With NO/NC contact
Thermostat with NC Contact:
b
b
to control the stopping of a resistance heater when the temperature exceeds the displayed value.
Thermostat with NO Contact:
b
b
to control the starting up of a fan when the temperature exceeds the displayed maximum value,
b
b
to control the temperature inside the enclosure by only starting up the fan when necessary, thus increasing the service life of the fan
and reducing the clogging of the filter.
Colour button
Red
Blue
Black
Red and blue
Ingress protection rating IP20
IP20
IP20
IP20
Sensor element
Bimetal
Bimetal
Bimetal
Bimetal
Contact
NC, forced rupture
NO, forced rupture
Inverse,forced rupture
NO / NC, forced rupture
Contact resistance
< 10 m
W
< 10 m
W
< 10 m
W
< 10 m
W
Service life
> 100,000 cycles
> 100,000 cycles
> 100,000 cycles
> 100,000 cycles
Switching capacity
250 V AC; 10 A (resistive load)
120 V AC; 15 A (resistive load)
250 V AC/120 V AC 2 A (inductive load cos = 0.6)
30 W DC
250 V AC; 10 A (resistive load)
250 V AC; 10 A (resistive load)
120 V AC; 15 A (resistive load)
250 V AC/120 V AC 2 A
(inductive load cos = 0.6)
30 W DC
Max interrupting
capacity with direct
current
NA
NA
250 V AC 4 A
(inductive load cos = 0.6)
30 W DC
NA
Connection
Two 2.5 mm
2
terminals
Two 2.5 mm
2
terminals
Four 2.5 mm
4
terminals
Six 2.5 mm
6
terminals
Mounting
By clip on 35 mm DIN rail
By clip on 35 mm DIN rail
By clip on 35 mm DIN rail
Clip on 35 mm DIN rail
Enclosure
UL 94 V-0 plastic, light grey
UL 94 V-0 plastic, light grey
UL 94 V-0 plastic, light grey
UL 94 V-0 plastic, light grey
Dimensions
60 x 33 x 43 mm
60 x 33 x 43 mm
67 x 50 x 44 mm
60 x 33 x 43 mm
Weight
40 g
40 g
100 g
40 g
Mounting position
Indifferent
Indifferent
Indifferent
Indifferent
Operating temperature -20...+80°C (-4...+176°F)
-20...+80°C (-4...+176°F)
-20...+80°C (-4...+176°F)
-20...+80°C (-4...+176°F)
Hysteresis
7°K
7°K
7°K
7°K
Temperature setting
range
0...+60°C
0...+60°C
+5...+60°C
0...+60°C
Display
°C
°F
°C
°F
°C
°F
°C
°F
Max. command intensity 10 A 250 V
(NO) 5 A (NC) 10 A
(NO) 5 A (NC) 10 A
References
NSYCCOTHC NSYCCOTHCF NSYCCOTHO NSYCCOTHOF NSYCCOTHI
NSYCCOTHIF NSYCCOTHD NSYCCOTHDF
DB300547-31
>
L N
2
1
Load
Load = resistance
DB300547-31
>
2
1
Load
L N Load = fan
DB300548-33
>
L N
Load
Load (2): resistance
Load (3): fan
Load
N2 L2
N1 L1
11
12
23
24
V
V
B
A
DB300549-32