Background Image
Table of Contents Table of Contents
Previous Page  25 / 132 Next Page
Information
Show Menu
Previous Page 25 / 132 Next Page
Page Background

25

Standard version

Long version

n

End feed units

Installation is carried out with a quick junction connection

The feed units have terminals for the connection of copper cables for

sections of up to 35 mm

2

for the 63/100 A feed unit and 70 mm

2

for the

160 A feed unit

The entrance point of the cables is positioned at the end of the feed unit

63 – 100 A

Tap-off boxes

Used to connect and energise single phase and three phase loads up

to 63 A. Features include :

• the PE contact (protective earth) is the first to make an electrical

connection when inserting the box into the outlet and it is the last to

disconnect when removing

• compliance with all insulating plastic components according to the

glow-wire test (IEC 60695-2-10) with V1 self-extinguishing degree

(UL94)

• standard IP 55 degree of protection without using additional

accessories

• can be inserted and removed when the busbar is energised and when

the fixture is under load, up to a capacity of 32 A

These boxes are available in a wide range of versions :

• 63 A empty boxes (only with a terminal board for connecting cables),

with an internal DIN rail and transparent door

• 16 A - available with a set of three cylindrical fuse carriers

(10·3 x 38 mm)

• 16/32 A - available with a set of three cylindrical fuse carriers -

DIAZED (D01 : 16 A; D02 : 32 A);

• 50 A – available with cylindrical fuse carriers (14 x 51 mm)

• 63 A – available with 4-7-16 DIN mod.

• 16 to 63 A – available with a disconnection device integral with the

cover

n

Centre feed units

63 – 100 A

160 A

160 A

125

85

d 1 = max. Ø 55

165

10

10

10

10

10

10

273

left

right

211

118

No. 2 d 1 = max. Ø 63

200

273

180

100

No. 2 d 1 = max. Ø 55

No. 2 d 1 =

max. Ø 55

273

8

8

270

273

200

120

No. 2 d 1 = max. Ø 63

No. 2 d 1 =

max. Ø 63

273

8

8

400

273

left

right

Max. cable

size 35 mm

2

Max. cable

size 70 mm

2

Max. cable

size 35 mm

2

6·5

6·5

Max. cable

size 25 mm

2

6·5

6·5

Max. cable

size 25 mm

2

10

10

Max. cable

size 35 mm

2

13

16

Max. cable

size 70 mm

2

d 1 max. = 38

160

97

150

d 1 max. = 38

160

97

250

10

10

Max. cable

size 35 mm

2

All dimensions (mm) are nominal