double sided busbar

technical data

27

Live conductors

No.

4

4

4

Casing overal dimension

A x B (mm)

39 x 97

39 x 97

39 x 97

Rated current

I

n

(A)

63

100

160

Cross-section of conductors (3P + N)

S (mm

2

)

26

26

39

Cross-section of protective conductor eq. Cu

S

PE

(mm

2

)

21

21

21

Operational voltage

U

e

(V)

400

400

400

Insulation voltage

U

i

(V)

750

750

750

Rated frequency

f (Hz)

50/60

50/60

50/60

Rated short-time current (0·1 s)

I

cw

(kA)rms

2·3

4·5

5·5

Peak current

Ipk (kA)

10

10

10

Maximum thermal limit

I

2

† (A

2

s x 106)

5·29

20·25

30·25

Phase resistance

R

20

(m

/m)

1·250

0·658

0·478

Phase reactance (50Hz)

X (m

/m)

0·366

0·366

0·247

Phase impedance

Z (m

/m)

1·302

0·753

0·538

Resistance of the protective bar

R

PE

(m

/m)

0·857

0·857

0·857

Reactance of the protective bar (50Hz)

X

PE

(m

/m)

0·090

0·090

0·102

Resistance of the fault loop

R

o

(m

/m)

1·85

1·26

1·08

Reactance of the fault loop (50Hz)

X

o

(m

/m)

0·456

0·456

0·349

Impedance of the fault loop

Z

o

(m

/m)

1·91

1·34

1·13

V (V/m/A)10-

3

cos

ϕ

= 0·70

0·98

0·63

0·44

∆∆

V (V/m/A)10-

3

cos

ϕ

= 0·75

1·02

0·64

0·45

∆∆

V (V/m/A)10-

3

cos

ϕ

= 0·80

1·06

0·65

0·46

∆∆

V (V/m/A)10-

3

cos

ϕ

= 0·85

1·09

0·65

0·46

∆∆

V (V/m/A)10-

3

cos

ϕ

= 0·90

1·11

0·65

0·47

∆∆

V (V/m/A)10-

3

cos

ϕ

= 0·95

1·13

0·64

0·46

∆∆

V (V/m/A)10-

3

cos

ϕ

= 1·00

1·08

0·57

0·41

Straight length weight

p (kg/m)

2·0

2·6

2·8

Fire load

(kWh/m)

1·64

1·64

1·64

Protection degree

IP

40/55

40/55

40/55

Losses for the Joule effect at full load

P (W/m)

14·9

19·7

36·7

Min./max. ambient temperature

† (°C)

-5/+50

-5/+50

-5/+50

Voltage drop with distributed load (k)

63

100

160

Rating (A)

(R

20

cos

ϕ

+ X sen

ϕ

)

V

3F

= 3

2

(2 R

20

cos

ϕ

+2 X sen

ϕ

)

V

1F

= 1

2

Suitable for the following climates :

Constant humid climate (DIN IEC 68 and 2- 3)

Cyclical humid climate (DIN IEC 68 and 2- 30)

Complies to :

IEC 439-1 and 2, BS EN 60439 part 1 and 2,

DIN VDE 0660 part 500 and 502

Short circuit protection for Zucchini product ranges (In

100 A)

Zucchini busbar systems with a nominal current less or equal to 100 A

(LB PLUS / MS 63 and 100 A) are correctly protected against short circuit

effects through an MCB (Miniature Circuit Breaker) with a nominal current

less or equal to the one of the busbar

This protection is assured up to MCB short circuit withstand

The busbar trunking systems LB PLUS / MS 63 and 100 A are flame

retardant in compliance with IEC 332-3 : 1992

Mean room temperature (°C)

15

20

25

30

35

40

45

50

55

60

K1 factor

1·15

1·12

1·08

1·05

1·025

1

0·975

0·95

0·93

0·89

Temperature rating schedule

Multiplier coefficient of nominal rating for room temperature values different from 40°C