Background Image
Table of Contents Table of Contents
Previous Page  92 / 108 Next Page
Information
Show Menu
Previous Page 92 / 108 Next Page
Page Background

92

Onix Plus™

Technical

screeded floor systems

customer services +44 (0)1745 532343

Onix Plus™ Floorboxes and Power Grommets

Metal Power grommet dimensions

The Metal Power Grommet is designed to be used in conjunction with the

Screed Base Unit, part number NXGB100-1 or NXGB100X-1, depending on

the depth of the screed.

Onix Grommets are are designed to be IP44 rated when the lid is closed,

allowing the floor to be washed.

Round Aluminium Floorbox

dimensions

This floorbox must be used in

conjunction with the 370x370mm

Onix Base Unit, 3 compartment

(

NXB370XUK-3)

Load Testing

Load Testing of Floorboxes to draft pr EN50085 Part 2-2 (Clauses 10.5.103

and 10.5.104).

The floorboxes have been tested to and comply with the loading requirements

of draft pr EN50085 Part 2-2 (Cable trunking systems and cable ducting

systems for electrical installations Part 2-2: Particular requirements for

cable trunking systems and cable ducting systems intended for mounting

underfloor, flushfloor, or onfloor).

There are two loading criteria for the floorboxes - one with a point loading

to replicate foot traffic for example, and the other, with a large plate to

replicate fork trucks and heavier larger loads for example. For both loading

criteria the maximum allowable deflection under load is 6mm and the

maximum permanent deflection after the load has been removed is 3mm.

The loading position is the centre of the lid.

The Lid Deflection (loading) graph shows that the maximum test wheel

loading classification achieved is 3kN and the maximum large plate loading

classification achieved is 10kN.

The Permanent Deflection graph shows the permanent deflection from

the test wheel loading at 3kN is 0.8mm and large plate loading at 10kN is

1.65

mm. This is well within the maximum allowable deflection of 3.0mm.

Note: This test data specifically refers to the 265x265mm sized cord outlet

box assembly. The other floorbox sizes also comply with the required test

criteria. Declarations of conformity are available on request for the entire

range.

Permanent deflection After Removal of Load

Onix Plus 265x265mm Cord Cap Lid

0

0.5

1

1.5

2

2.5

3

3.5

Large Plate Load (10kN)

Point Load (3kN)

Permanent Deflection (mm)

Maximum Allowable Permanent

Deflection (3mm)

Maximum Allowable Deflection

(6

mm)

Point Loading (10kN)

Plate Loading (3kN)

0

1

2

3

4

5

6

7

1

2

3

4

5

6

7

8

9

10

Load (kN)

Deflection Under Load (mm)

Lid deflection - Onix Plus Cord Outlet Lid 265x265mm

120

mm

120

mm

96

mm

200

mm

110

mm

96

mm

BASE UnIT

nxgB100-1

nxgB100x-1

Screed Depth (mm)

55-80

mm

80-110

mm

319

mm

303

mm

Cut out dimension