overhead systems

customer services +44 (0)1745 532343

Interact Overhead

Technical

Interact Overhead Power

Technical Specification

Overhead 40A –

Manufactured within ISO 9000 environment.

Electrical Characteristics

Overhead

Rated Current

40

A

Rated Voltage

480

V

Frequency

50/60

Hz

Conditional Short Circuit Rating

16

kA

Resistance per Copper Conductor

(

At ambient temperature 20ºC)

1.3

m

Ω

/

m

Impedance per Copper Conductor

(

At ambient temperature 20ºC)

1.3

m

Ω

/

m

Volt Drops (Full load, concentrated at one end)

Powertrack (Line + Neutral)

2.9

mV/A/m

Feed Unit

0.3

mV/A

Tap-off Connection

1.6

mV/A

+ 2.5mm

2

Cable

18

mV/A/m

Joint

0.3

mV/A

Flexible Interlink Unit

0.8

mV/A

+ 6mm

2

Cable

7.0

mV/A/m

Mechanical Data

Max. No. of Copper Conductors

5

Conductor Cross Section Area Nominal

14.4

mm

2

Powertrack Casing Copper Equivalent

(

Where Casing is Protective Earth)

12.0

mm

2

Cable Termination Capacity

10

mm

2

Tap-off Cable

2.5

mm

2

Flexible Interlink Cable

6

mm

2

Flexible Interlink Conduit

25

Ømm

Feed Conduit Entry

20

Ømm

IP Rating

2

X

Materials Specification

Powertrack Casing, Feeds and Brackets Galvanised Steel

Conductors

High Conductivity Copper

Powertrack Insulators

40

A Polyamide and Polyester

Sockets/Tap-off Plug/Joint Mouldings

Modified PPO

Shutter

Polyacetal

Interlink Flexible Conduit

Galvanised Steel

Tap-off Cable

Multi-core Cable to BS 6500 and

BS 7211. LSF Cable standard,

PVC Cable available on request

Tap-off Pins

Line, Neutral & Copper Earth

Copper and Phosphorous

Bronze, tin plated

Casing Earth

Brass, tin plated

Flexible Interlink Cable

Tri-Rated to BS 6231