Cablelink Plus Screed

Technical

screeded floor systems

customer services +44 (0)1745 532343

Cablelink Plus Screed System

Load Testing

Load Testing of Floorboxes to EN50085 Part 2-2 (Clauses 10.5.103 and

10.5.104).

The floorboxes have been tested to and comply with the loading requirements

of EN50085 Part 2-2 (Cable trunking systems and cable ducting systems for

electrical installations Part 2-2: Particular requirements for cable trunking

systems and cable ducting systems intended for mounting underfloor,

flushfloor, or onfloor).

There are two loading criteria for the floorboxes - one with a point loading

to replicate foot traffic for example, and the other, with a large plate to

replicate fork trucks and heavier larger loads for example. For both loading

criteria the maximum allowable deflection under load is 6mm and the

maximum permanent deflection after the load has been removed is 3mm.

The Lid Deflection (loading) graph shows that the maximum point loading

classification achieved is 3kN and the maximum large plate loading

classification achieved is 5kN.

The Permanent Deflection graph shows the permanent deflection from the

test wheel loading at 2kN is 0.3mm and large plate loading at 5kN is 0.4mm.

This is well within the maximum allowable deflection of 3.0mm.

Note: This test data specifically refers to the 265x265mm sized floorbox

frame assembly. The other floorbox sizes also comply with the required test

criteria. Declarations of conformity are available on request for the entire

range.

Cat 6 Compatibility

With the introduction of Cat 6 data cabling the orientation and depth of

many data outlets has changed resulting in the need for greater backbox

depths and wiring space to accommodate these longer data outlet. No

longer is a 35mm wiring space sufficient to ensure data terminations can

be made to the manufacturer’s recommendations to prevent transmission

losses. As a result MK has introduced 45mm wiring space for the Cablelink

Plus Floorbox systems (as well as for the Prestige 3D wall trunking system).

This easily accommodates the longer Cat 6 data outlets and leaves sufficient

space for the data cable to run underneath it.

Lid Deflection – Cablelink Plus 265x265mm

Frame Assembly

Permanent Deflection After Removal of Load

Cablelink Plus 265x265mm Frame

0

1

2

3

4

5

6

0.5

1

1.5

2

2.5

3

3.5

4

Load (kN)

Deflection under Load (mm)

Point Loading

Plate Loading

Maximum Allowable Deflection

Under Load (6mm)

7

4.5

5

0

0.5

1

1.5

2

2.5

3

3.5

Large Plate Load (5kN)

Point Load (3kN)

Permanent Deflection (mm)

Maximum Allowable

Permanent Deflection (3mm)