BETA Monitoring

Monitoring of Plants and Devices

7

LQ2 1, 5TT3 3 dusk switches

14/20

Siemens ET B1 · 10/2008

14

Overview

Dusk switches are used for the demand-oriented switching of

lighting installations for shop windows or paths in order to cut

operating costs.

A light sensor measures the level of daylight. Switching depends

on the desired brightness. A time delay and the switching

hysteresis prevent clock-pulse behavior.

The sensor must be mounted so that it is not influenced by the

lighting feedback.

Benefits

The 7LQ2 101 and 7LQ2 103 devices have 2 switching channels

that can be set independently of each other. This requires a

light sensor

• 12

dusk switches can be switched parallel to a light sensor.

This saves the multiple installation of light sensors in a single

system and all dusk switches operate independently of each

other and can be adjusted individually.

Technical specifications

7

LQ2 100 7LQ2 101

7

LQ2 102 7LQ2 103

5

TT3 303

Standards

EN 60730

Rated control voltage U

c

V AC 230

Operating range

At 50/60 Hz

× U

c

0.8 ... 1.2

Rated frequency f

n

Hz

45 ... 65

Measuring ranges, setting ranges

Lux

2 ... 500 2

× 2 ... 500 2 ... 500 2 × 2 ... 500 2 ... 2000

Time delay

Non-adjustable

s

75

± 25 No

75

± 25 No

50

Adjustable

No

2

× 50 ... 100

± 25

No

2

× 50 ... 100

± 25

No

Status indication, LED

Switching status indication

Instantaneous

No

Switching state OFF

Green

No

Switching state ON

Red

No

Incandescent lamp load

W 2000

2

× 2000

2000

2

× 2000

1200

Different phases

Actuator/contact permissible

Yes

No

Contact/contact

No

Yes

No

Yes

No

Electrical isolation

Creepage distances and

clearances

Actuator/contact

mm 4

No

Contact/contact

mm No

4

No

4

No

Rated impulse withstand voltage U

imp

Actuator/contact

kV

> 2.5

No

1.2/50

s

Contact/contact

kV

No

> 2.5

No

> 2.5

No

Contacts

contact

1

NO 2 NO

1

NO 2 NO

1

NO

Rated operational voltage U

e

V AC 250

Rated operational current

I

s

-

At p.f. = 1

A

16

10

-

At p.f. = 0.4

A

4

2

Minimum contact load

V; mA 10; 100

Contact switching

Closes with approaching

darkness

Terminals 3/4

5/6

and 9/10 3/4

5/6

and 9/10 No

Terminals

Terminals

±

screw (Pozidriv)

PZ 1

Conductor cross-sections

-

Rigid

mm

2

1.5 ... 6

1.5

-

Flexible, with end sleeve

Min.

mm

2

0.75

0.5

Environmental conditions

Permissible ambient temperature

-

Device

°C

-10 ...

+55

-

Light sensor

°C

-30 ...

+70

--

Permissible humidity

-

Device

%

< 80

-

Light sensor

%

< 98

--

Degree of protection

Acc. to EN 60529

-

Device

IP20, with connected conductors

IP54

-

Light sensor

IP55

IP65

No

Safety class

Acc. to EN 61010

II

© Siemens AG 2008