Background Image
Table of Contents Table of Contents
Previous Page  51 / 543 Next Page
Information
Show Menu
Previous Page 51 / 543 Next Page
Page Background

Busbar system

D fuse switch-disconnector

2010 CA08103002Z-EN

www.eaton.com

SASY

16/47

SASYD fuse switch-disconnector

D02-S/63/3-RS

D02-LTS/63/3-R(-HK)

General

Standards

Design according to IEC/EN 60947-3

Climatic proofing

Damp heat, constant, to IEC 60068-2-78, Damp heat, cyclical to IEC 60068-2-30

Ambient temperature

°C

-25 - +55

-25 - +55

Mounting position

Vertical or horizontal

Electrical data

Poles

3

3

Rated operating voltage

U

e

V AC 400

400

U

e

V DC –

Rated short-circuit current, tested with fuse links

I

q

kA

50

63

Rated frequency

f

Hz

40-60

40-60

Rated operational current

I

e

A

63

63

Conventional thermal current with fuse links

I

th

A

63

63

Rated operating mode

Continuous operation

Rated short-circuit switching capacity

I

cn

kA

50

Overvoltage category

III

IV

Utilization category

AC 23 B

AC 22 B

Rated impulse withstand voltage

U

imp

kV

8

6

Current heat dissipation per contact at I

e

W 2

1.5

Heat dissipation

Heat dissipation per contact with fuse link at I

e

W 7.5

7

Max. permissible heat dissipation of fuse links

W 5.5

5.5

Auxiliary contacts

Changeover contacts

Number –

5A/250 V AC

Back-up fuse

A gL

2 A gL

PLSM-B4/…-HS/CLS6-B4/…-HS

Connection

Blade terminal sleeve 2.8 x 0.5 mm

Mechanical data

Standard front dimension

mm 194

194

Enclosure width

mm 212

226

Built-in width

mm 36

27

Weight

g

260

340

Electric thread

E18

Mounting

Busbar with 60 mm clearance

Degree of protection

Integrated

IP30

IP20/IP40

Terminals

Lift terminals

Lift terminals

Terminal capacity

Solid

mm

2

1.5 - 25

1.5 - 35

Pollution degree

3

3

Creepage resistance

D02-S..., D02-LTS...