17/186 SmartWire-Darwin

SWD input/output modules

2010 CA08103002Z-EN

www.eaton.com

SWD input/outputmodules

SWD input/outputmodules

NZM-XSWD-704

General

Standards

IEC/EN 61131-2

EN 50178

Dimensions (W x H x D)

mm

35 x 90 x 101

Weight

kg

0.1

Mounting

Top-hat rail IEC/EN 60715, 35 mm

Built-in position

Vertical

Ambient mechanical conditions

Degree of protection (IEC/EN 60529)

IP20

Vibrations (IEC/EN 61131-2:2008)

Constant amplitude 3.5 mm

Hz

5 … 8.4

Constant acceleration, 1 g

Hz

8.4 … 150

Mechanical shock resistance (IEC/EN 60068-2-27)

semi-sinusoidal 15 g/11 ms

Shocks

9

Drop (IEC/EN 60068-2-31)

Drop height

mm

50

Free fall, packaged (IEC/EN 60068-2-32)

m

0.3

Electromagnetic compatibility (EMC)

Overvoltage category

II

Pollution degree

2

Electrostatic discharge (IEC/EN 61131-2:2008)

Air discharge (Level 3)

kV

8

Contact discharge (Level 2)

kV

4

Electromagnetic fields (IEC/EN 61131-2:2008)

80 -1000 MHz

V/m

10

1.4-2 GHz

V/m

3

2-2.7 GHz

V/m

1

Radio interference suppression (SmartWire-Darwin)

EN 55011 Class A

Burst (IEC/EN 61131-2:2008, Level 3)

Supply cables

kV

2

Signal cables

kV

1

SmartWire-Darwin cables

kV

1

Surge (IEC/EN 61131-2:2008, Level 1)

Radiated RFI (IEC/EN 61131-2:2008, Level 3)

V

10

Ambient climatic conditions

Operating ambient temperature (IEC 60068-2)

°C

–25 … +55

Condensation

Prevent with suitable measures

Storage

°C

–40…70

Relative humidity, non-condensing (IEC/EN 60068-2-30)

%

5 … 95

SmartWire-Darwin interface

Station type

SmartWire-Darwin station (slave)

Baud rate setting

Automatic

SmartWire-Darwin status

LED

Green

Connection

8-pin connector

Connection plug: External device plug

SWD4-8SF2-5

Power consumption (15 V SWD supply)

See separate table

Supply and I/O connection

Connection type

Push-In

Solid

mm

2

0.2-1.5 (AWG 24-16)

Flexible with ferrule

1)

mm

2

0.25-1.5

24 V DC supply for output supply

Rated operating voltage

U

e

V

Input voltage residual ripple

%

Polarity reversal protection reversal

Notes

1)

Minimum length 8 mm.