17/186 SmartWire-Darwin
SWD input/output modules
2010 CA08103002Z-EN
www.eaton.comSWD input/outputmodules
SWD input/outputmodules
NZM-XSWD-704
General
Standards
IEC/EN 61131-2
EN 50178
Dimensions (W x H x D)
mm
35 x 90 x 101
Weight
kg
0.1
Mounting
Top-hat rail IEC/EN 60715, 35 mm
Built-in position
Vertical
Ambient mechanical conditions
Degree of protection (IEC/EN 60529)
IP20
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3.5 mm
Hz
5 … 8.4
Constant acceleration, 1 g
Hz
8.4 … 150
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15 g/11 ms
Shocks
9
Drop (IEC/EN 60068-2-31)
Drop height
mm
50
Free fall, packaged (IEC/EN 60068-2-32)
m
0.3
Electromagnetic compatibility (EMC)
Overvoltage category
II
Pollution degree
2
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3)
kV
8
Contact discharge (Level 2)
kV
4
Electromagnetic fields (IEC/EN 61131-2:2008)
80 -1000 MHz
V/m
10
1.4-2 GHz
V/m
3
2-2.7 GHz
V/m
1
Radio interference suppression (SmartWire-Darwin)
EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
Supply cables
kV
2
Signal cables
kV
1
SmartWire-Darwin cables
kV
1
Surge (IEC/EN 61131-2:2008, Level 1)
–
Radiated RFI (IEC/EN 61131-2:2008, Level 3)
V
10
Ambient climatic conditions
Operating ambient temperature (IEC 60068-2)
°C
–25 … +55
Condensation
Prevent with suitable measures
Storage
°C
–40…70
Relative humidity, non-condensing (IEC/EN 60068-2-30)
%
5 … 95
SmartWire-Darwin interface
Station type
SmartWire-Darwin station (slave)
Baud rate setting
Automatic
SmartWire-Darwin status
LED
Green
Connection
8-pin connector
Connection plug: External device plug
SWD4-8SF2-5
Power consumption (15 V SWD supply)
See separate table
Supply and I/O connection
Connection type
Push-In
Solid
mm
2
0.2-1.5 (AWG 24-16)
Flexible with ferrule
1)
mm
2
0.25-1.5
24 V DC supply for output supply
Rated operating voltage
U
e
V
–
Input voltage residual ripple
%
–
Polarity reversal protection reversal
–
Notes
1)
Minimum length 8 mm.
NZM-XSWD