Electronic Overload Relays to 1500 A

2010

CA08103002Z-EN

www.eaton.com

6/33

ZEB12, ZEB32

ZEB65-45

ZEB65-100

ZEB150

General

Standards

IEC/EN 60947, VDE 0660, UL, CSA

Climatic proofing

Damp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature

Open

°C

–25…65

–25…65

–25…65

–25…65

Enclosed

°C

–25…65

–25…40

–25…40

–25…40

Temperature compensation

Continuous

Continuous

Continuous

Continuous

Mounting position

Any

Any

Any

Any

Mechanical shock resistance half-sinusoidal shock, 10 ms

to IEC 60068-2-27

g

15

15

15

15

Protection type

IP20

IP20

IP20

IP20

Protection against direct contact when actuated

from front (EN 50274)

Finger- and back-of-hand proof

Main contacts

Rated impulse withstand voltage

U

imp

V AC 6000

6000

6000

6000

Overvoltage category/pollution degree

III / 3

III / 3

III / 3

III / 3

Rated insulation voltage

AC

U

i

V AC 690

690

690

690

Rated operating voltage

U

e

V AC 690

690

690

690

Safe isolation according to EN 61140

Between auxiliary contacts and main contacts

V AC 600

600

600

600

Between the main contacts

V AC 600

600

600

600

Overload relay setting range

A

0.3…45

9…45

20…100

20…100

Terminal capacity

Solid

mm

2

1

x 2.5 - 16

1

x 2.5 - 16

1

x 6 - 50

1

x 6 - 50

Solid or stranded

AWG 1 x 14 - 4

1

x 14 - 4

1

x 10 - 1

1

x 10 - 1

Auxiliary and control circuits

Rated impulse withstand voltage

U

imp

V

6000

6000

6000

6000

Overvoltage category/pollution degree

III / 3

III / 3

III / 3

III / 3

Terminal capacity

Solid

mm

2

2

x (0.75 - 4)

2

x (0.75 - 4)

2

x (0.75 - 4)

2

x (0.75 - 4)

Flexible with ferrule

mm

2

2

x (0.75 - 2.5)

2

x (0.75 - 2.5)

2

x (0.75 - 2.5)

2

x (0.75 - 2.5)

Solid or stranded

AWG 2 x (18 - 12)

2

x (18 - 12)

2

x (18 - 12)

2

x (18 - 12)

Terminal screw

M3.5

M3.5

M3.5

M3.5

Tightening torque

Nm 0.8 - 1.2

0.8 - 1.2

0.8 - 1.2

0.8 - 1.2

lb-in

7 - 10.6

7 - 10.6

7 - 10.6

7 - 10.6

Tools

Pozidriv screwdriver

Size

2

2

2

2

Flat-blade screwdriver

mm 1 x 6

1

x 6

1

x 6

1

x 6

Auxiliary circuit rated insulation voltage

U

i

V AC 500

500

500

500

Rated operating voltage

U

e

V AC 500

500

500

500

Safe isolation according to EN 61140

Between the auxiliary contacts

V AC 240

240

240

240

Conventional thermal current

I

th

A

5

5

5

5

Rated operational current

AC-15

N/O

120

V

I

e

A

1.5

1.5

1.5

1.5

240

V

I

e

A

1.5

1.5

1.5

1.5

415

V

I

e

A

0.5

0.5

0.5

0.5

500

V

I

e

A

0.5

0.5

0.5

0.5

NC

120

V

I

e

A

1.5

1.5

1.5

1.5

240

V

I

e

A

1.5

1.5

1.5

1.5

415

V

I

e

A

0.9

0.9

0.9

0.9

500

V

I

e

A

0.8

0.8

0.8

0.8

DC-13 L/R ≦ 15 ms

24

V

I

e

A

0.9

0.9

0.9

0.9

60

V

I

e

A

0.75

0.75

0.75

0.75

110

V

I

e

A

0

0.4

0.4

0.4

220

V

I

e

A

0.2

0.2

0.2

0.2

Short-circuit rating without welding

Max. fuse

A gG/gL 6

6

6

6

ZEB