Electronic Overload Relays to 1500 A
2010
CA08103002Z-EN
www.eaton.com6/33
ZEB12, ZEB32
ZEB65-45
ZEB65-100
ZEB150
General
Standards
IEC/EN 60947, VDE 0660, UL, CSA
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open
°C
–25…65
–25…65
–25…65
–25…65
Enclosed
°C
–25…65
–25…40
–25…40
–25…40
Temperature compensation
Continuous
Continuous
Continuous
Continuous
Mounting position
Any
Any
Any
Any
Mechanical shock resistance half-sinusoidal shock, 10 ms
to IEC 60068-2-27
g
15
15
15
15
Protection type
IP20
IP20
IP20
IP20
Protection against direct contact when actuated
from front (EN 50274)
Finger- and back-of-hand proof
Main contacts
Rated impulse withstand voltage
U
imp
V AC 6000
6000
6000
6000
Overvoltage category/pollution degree
III / 3
III / 3
III / 3
III / 3
Rated insulation voltage
AC
U
i
V AC 690
690
690
690
Rated operating voltage
U
e
V AC 690
690
690
690
Safe isolation according to EN 61140
Between auxiliary contacts and main contacts
V AC 600
600
600
600
Between the main contacts
V AC 600
600
600
600
Overload relay setting range
A
0.3…45
9…45
20…100
20…100
Terminal capacity
Solid
mm
2
1
x 2.5 - 16
1
x 2.5 - 16
1
x 6 - 50
1
x 6 - 50
Solid or stranded
AWG 1 x 14 - 4
1
x 14 - 4
1
x 10 - 1
1
x 10 - 1
Auxiliary and control circuits
Rated impulse withstand voltage
U
imp
V
6000
6000
6000
6000
Overvoltage category/pollution degree
III / 3
III / 3
III / 3
III / 3
Terminal capacity
Solid
mm
2
2
x (0.75 - 4)
2
x (0.75 - 4)
2
x (0.75 - 4)
2
x (0.75 - 4)
Flexible with ferrule
mm
2
2
x (0.75 - 2.5)
2
x (0.75 - 2.5)
2
x (0.75 - 2.5)
2
x (0.75 - 2.5)
Solid or stranded
AWG 2 x (18 - 12)
2
x (18 - 12)
2
x (18 - 12)
2
x (18 - 12)
Terminal screw
M3.5
M3.5
M3.5
M3.5
Tightening torque
Nm 0.8 - 1.2
0.8 - 1.2
0.8 - 1.2
0.8 - 1.2
lb-in
7 - 10.6
7 - 10.6
7 - 10.6
7 - 10.6
Tools
Pozidriv screwdriver
Size
2
2
2
2
Flat-blade screwdriver
mm 1 x 6
1
x 6
1
x 6
1
x 6
Auxiliary circuit rated insulation voltage
U
i
V AC 500
500
500
500
Rated operating voltage
U
e
V AC 500
500
500
500
Safe isolation according to EN 61140
Between the auxiliary contacts
V AC 240
240
240
240
Conventional thermal current
I
th
A
5
5
5
5
Rated operational current
AC-15
N/O
120
V
I
e
A
1.5
1.5
1.5
1.5
240
V
I
e
A
1.5
1.5
1.5
1.5
415
V
I
e
A
0.5
0.5
0.5
0.5
500
V
I
e
A
0.5
0.5
0.5
0.5
NC
120
V
I
e
A
1.5
1.5
1.5
1.5
240
V
I
e
A
1.5
1.5
1.5
1.5
415
V
I
e
A
0.9
0.9
0.9
0.9
500
V
I
e
A
0.8
0.8
0.8
0.8
DC-13 L/R ≦ 15 ms
24
V
I
e
A
0.9
0.9
0.9
0.9
60
V
I
e
A
0.75
0.75
0.75
0.75
110
V
I
e
A
0
0.4
0.4
0.4
220
V
I
e
A
0.2
0.2
0.2
0.2
Short-circuit rating without welding
Max. fuse
A gG/gL 6
6
6
6
ZEB