Background Image
Table of Contents Table of Contents
Previous Page  18 / 439 Next Page
Information
Show Menu
Previous Page 18 / 439 Next Page
Page Background

5/14

Contactors

2010

CA08103002Z-EN

www.eaton.com

Technical overview

Contactors

3

pole

DIL

EEM EM EM12 M7 M9 M12 M15 M17 M25 M32 M38 M40 M50 M65 M80 M95 M115 M150 M170

Basic devices

Page

→5/4

→5/18

→5/18

→ 5/20

→5/50

Complete units

Page

→Page 5/24

→Page 5/24

→Page 5/26

→Page 5/26

Rated-operational

voltage

kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

AC-3

Rated operational power

for 3-phase motors 50 –60 Hz

220

V – 230 V

1.5 2.2 3

2.2 2.5 3.5 4

5

7.5 10 11 12.5 15.5 20 25 30 37

48

52

380

V – 400 V

3

4 5.5 3 4

5.5 7.5 7.5 11 15 18.5 18.5 22 30 37 45 55

75

90

440

V

3.3 4.6 5.5 4.5 5.5 7.5 8.4 10.5 15.5 20 21 25 32 41 51 60 75

95

105

500

V

3

4 5.5 3.5 4.5 7

7.5 12 17.5 23 24 28 36 47 58 70 85

110 120

660

V/690 V

3

4 4

3.5 4.5 6.5 7

11 14 17 21 23 30 35 63 75 90

96

140

1000

V

– – –

– – – – – – – – – – – – – –

AC-4

Rated operational power

for 3-phase motors 50 –60 Hz

 Increase in life span for DILM7 – DILM150 to 200000 operations

220

V – 230 V

1.1 1.5 1.5 1 1.5 2

2

2.5 3.5 4

4

5

6

7

12 16 17

20

20

380

V – 400 V

2.2 3 3

2.2 2.5 3

3

4.5 6

7

7

9

10 12 20 26 28

33

33

440

V

2.4 3.3 3.3 2.4 3

3.6 3.6 5.5 7

8

8

10 12 14 25 32 35

41

41

500

V

2.2 3 3

2.5 2.8 3.5 3.5 6

8

9

9

11 13 16 29 36 40

47

47

660

V/690 V

2.2 3 3

2.9 3.6 4.4 4.4 6.5 8.5 10 10 12 14 17 26 35 43

48

48

1000

V

– – –

– – – – – – – – – – – – – –

AC-1

Rated operational power under resistive load, 40 °C

220

V – 230 V

8

8 8

8 8

8

8

15 17 17 17 22 30 37 42 49 61

72

85

380

V – 400 V

13 13 13

14 14 14 14 26 29 29 29 39 53 65 72 85 105 125 150

440

V

15 15 15

16 16 16 16 30 34 34 34 45 58 71 80 94 116 138 170

500

V

18 18 18

19 19 19 19 34 38 38 38 51 66 81 90 107 132 156 194

660

V/690 V

23 23 23

25 25 25 25 45 51 51 51 68 91 111 125 148 182 216 268

1000

V

– – –

– – – – – – – – – – – – – –

Conventional thermal

Current

I

th

= I

e

open at 40 °C

A A A A A A A A A A A A A A A A A A A

22 22 22

22 22 22 22 40 45 45 45 60 80 98 110 130 160 190 225

Contactors

4

pole

DIL

EM4

MP20

MP32

Rated operational voltage

Page

→5/4

→Page 5/36

→Page 5/36

AC-1

Conventional free air thermal current I

th

= I

e

open, at 40 °C

A

A

A

up to 690 V

22

22

32

DILM, DILE(E)M, DILMP